Carrier 61CW-Z Installation, Operation And Maintenance Instructions page 15

Table of Contents

Advertisement

6 - OPERATION
Outputs:
■ Compressor status message (compressor running)
■ Fault message (heat pump has a fault)
■ Message of readiness for operation (the heat pump is ready 
for operation, i.e. switched on and fault-free, and may be started 
at any time via remote ON/OFF)
■ Compressor running at 100 % output 
■ Enables  external  control  of  a  3-way  valve  on  the  condenser 
(when the 3-way valve is not switched by the heat pump) 
■ Enables external control of a 3-way valve on the evaporator 
(when the 3-way valve is not switched by the heat pump) 
■ 0-10 V differential temperature, condenser (pump control unit)
■ 0-10 V differential temperature, evaporator (pump control unit)
6.2.3 - Control of peripherals:
In this context, peripherals are circulation pumps on the source 
(evaporator) and condenser side.
Control by CARRIER heat pump:
The external source and condenser pumps can be controlled by 
the heat pump controller. The required prerun and overrun times 
are set by CARRIER customer service for each specific application.
The type of control is specified in the system datasheet. 
Control via external building management system:
The external BMS fully regulates the targets, controls the system 
peripherals  (pumps,  dampers,  valves,  etc.)  and  only  requests 
active heating or cooling from the heat pump.
In this context, the following functions must be ensured:
■ The source pump must be started approximately 1.0 minute 
prior to the heat pump being enabled and must run on for around 
1.0 minute after the compressor has stopped (feedback signal).
■ The condenser pump (consumption side) must start up at least 
0.5 minutes before the compressor and run on for at least 0.5 
minutes.
■ The compressor must not be switched more than 4 times per 
hour.
■ The standard minimum operating time must not fall below 10 
minutes. 
To  the  extent  required,  the  external  BMS  receives  a  feedback 
signal about the actual operating state of the compressor by means 
of a floating contact (standby, compressor running or safety shut 
down). The source and condenser pumps must always run when 
the compressor is working to prevent faults and damage to the 
heat pump. We recommend linking the prerun and overrun timers 
to the enable and feedback signals.
If the source and condenser pumps assume other functions outside 
heat pump operation, it makes sense to have the external BMS 
control these circulation pumps.
Control of 3-way valves by CARRIER heat pump:
The heat pump control unit can regulate the voltage supply to and 
switching of the external 3-way mixing valves (actuators), both on 
the  source  and/or  condenser  side.  In  the  standard  version,  the 
heat pump issues a 0-10 V target signal to switch the 3-way valves 
on the evaporator and/or condenser side. 
A 4-20 mA signal can also be provided as an option. The 3-way 
valves or their actuators must be installed so that they are 100% 
open to a hydraulic system on the source or consumption at a 10 
V target signal. When the target signal is 0 V, the valves should 
be fully open towards the bypass (short circuit circulation). 
A voltage supply is provided to drive the 3-way valves. This can 
be either 24 V DC (standard) or 24 V AC.
The voltage supply and type of control are defined in the system 
datasheet and may vary from the standard version.
The 3-way valves used must reach an actuating time (duration 
from fully open to fully closed state and vice versa) of maximum 
30 seconds, 16 seconds is better.
6.2.4 - Buffer tank
The text below describes the heat pump in heating mode as an 
example (target at condenser outlet), but it applies vice versa to 
cooling mode (target at evaporator outlet). 
Note that, depending on the hydraulic system and the temperature 
spread, the heat pump target (condenser outlet) generally has to 
be higher than the required temperature in the buffer tank. If for 
example a temperature of 60°C is to be reached in the heating 
buffer tank, the heat pump should generally be set a target value 
>60°C (temperature raising). 
Once  the  buffer  tank  has  been  heated  to  approximately  the 
required  target  temperature  and  the  heat  pump  is  off/shutting 
down, the heat pump should remain off (via the remote ON/OFF) 
until  the  buffer  tank  has  cooled  down  again  or  the  agreed 
temperature  spread  across  the  condenser  could  be  controlled 
again at least over the minimum runtime. 
If, for example, the target temperature for the condenser outlet is 
60°C and the agreed temperature spread between condenser inlet 
and condenser outlet is 10K, the heat pump should only run when 
the temperature at the condenser inlet is 50°C or less.
If, for example, the target temperature for the evaporator outlet is 
8°C and the agreed temperature spread between evaporator inlet 
and evaporator outlet is 10K, the heat pump should only run when 
the temperature at the evaporator inlet is 18°C or more. 
15

Advertisement

Table of Contents
loading

Table of Contents