This product emits radiation in the infrared range and uses LASER technology. It has been developed to meet the class 1 requirements of IEC 60825- 1:2014 (Third Edition). Provided that the user follows NOVUS recommendations described in this manual, the radiation emission will remain within the limits of class 1.
PRESENTATION TL400-I is a non-intrusive level transmitter with no moving parts, using an infrared laser technology (~920 nm) that is completely safe to the human eye (LASER CLASS-1). Its measurement principle is based on ToF (Time of Flight), providing an accurate and reliable distance measurement, regardless of the color or transparency of the surface .
QR Code. Figure 2 – Equipment identification TL400-I TL400-I is suitable for industrial installation. It can be installed on a tank lid and has a cable with an M12 connector. Figure 3 – TL400-I NOVUS AUTOMATION...
The output connector is a M12 type with the following wiring connections: Figure 4 – Electrical connections 4.1.3 DIMENSIONS 4.1.3.1 TL400-I The figures below show the dimensions of the TL400-I and an overview of the equipment: Figure 5 – Dimensions NOVUS AUTOMATION 6/26...
3. Make the connections: After placing the equipment in the desired location, tighten the screws and then make the electrical connections (see ELECTRICAL CONNECTIONS section). 4. Configure: Use the SigNow app to configure the equipment (see SIGNOW APP chapter). NOVUS AUTOMATION 7/26...
4.2.1 TL400-I WITH AND WITHOUT ADAPTER The figures below show versions of the equipment with and without the adapter (optional accessory): Figure 9 – TL400-I Figure 10 – TL400-I with adapter To install the adapter and the gasket, the correct position must be observed: Figure 11 –...
Page 9
Figure 13 – Examples of improper installations TL400-I is not recommended for applications in environments with direct sunlight. In such cases, measurement may be affected. NOVUS AUTOMATION 9/26...
Figure 15 – Types of tanks If the options do not fit the type of tank being used, TL400-I also allows you to create custom tanks. This feature is useful for tanks that are shaped with curves, rises, and other irregularities.
Page 11
To check if the curve is in accordance with the set value, you can follow the path Diagnostics > Advanced > Forcing and force a distance, which will allow you to analyze if the analog output response is adequate. Figure 17 – Filter NOVUS AUTOMATION 11/26...
SIGNOW APP SigNow app is the ideal tool to use your TL400-I on a daily basis. Available for Android and iOS smartphones, it allows you to configure or perform diagnostics on the equipment. Connection to the equipment can be made via the Bluetooth interface.
By clicking the Manual button, you will be redirected to the online manual for the equipment. By clicking the Support button, you will be redirected to NOVUS Technical Support page. The Send button allows you to send the settings to the equipment.
By clicking the Advanced button, SigNow will display sections regarding the advanced configuration of the equipment: Here you can select the parameter group to be configured: Input, Output, Advanced Filter, or Security. You can also change the equipment tag. Figure 21 – Advanced configuration NOVUS AUTOMATION 14/26...
When configured to Custom, the calibrated points should go from the greatest distance to the smallest distance (smallest volume to greatest volume), as shown in the example below: POINT DISTANCE VOLUME (%) Calibration points Figure 23 – Volume advanced configurations NOVUS AUTOMATION 15/26...
Low (4 mA) • High (20 mA) • None • Low/High (4 mA / 20 mA) • In addition, you can set a minimum value and a maximum value for the output. Figure 25 – Output advanced configurations NOVUS AUTOMATION 16/26...
By clicking on a specific parameter to configure it, as shown in the examples opposite, you can see explanations of how to use it. These explanations are also shown in detail in the ADVANCED FILTER chapter. Figure 27 – Definitions NOVUS AUTOMATION 17/26...
None of this information is editable. By clicking the Manual button, you will be redirected to the online manual for the equipment. By clicking the Support button, you will be redirected to NOVUS Technical Support page. Figure 29 – Diagnostic – Info The Advanced button is in the lower right corner of the Info screen.
Page 19
By selecting one of the forcing options in the section above, you will be redirected to the appropriate screen, where you can set specific values for each parameter: Figure 31 – Forcing: Distance Figure 32 – Forcing: Level Figure 33 – Forcing: Volumen Figure 34 – Forcing: Analog Output NOVUS AUTOMATION 19/26...
By clicking on the Check Files Online button, located in the right corner of the screen, you can check online for firmware files. After that, simply select the file to be used by SigNow and perform the update process. Figure 37 – Selecting a file NOVUS AUTOMATION 20/26...
If the sensor is "missing too much" when collecting data, it is possible to reduce this difference by selecting a smaller position, using a Median index value that is less than 0. NOVUS AUTOMATION 21/26...
This parameter allows you to reduce the oscillation or data peaks of the analog output. When it collects a new value, it analyzes the acceptance rate, which is why this new value will be accepted. If it is 1, the new value accepted will be the new value itself. If it is 2, it will be half the new value. NOVUS AUTOMATION 22/26...
Then, in Diagnostic > Advanced, you can check the volume according to the distance, depending on the configured calibration. When using the custom curve, the tank height value will be ignored for the volume calculation. Figure 42 – Configuration (1) Figure 43 – Configuration (2) Figure 44 – Configuration (3) Figure 45 – Configuration (4) NOVUS AUTOMATION 23/26...
TECHNICAL SPECIFICATIONS FEATURES TL400-I Dimensions 241.7 x 66 x 31 mm Distance Measurement Configurable from 0 to 4000 mm. Resolution Maximum of 30 mm but can reach a minimum of 1 mm if in good measuring conditions. Sampling 1 Hz Connector M12 with 4 pins.