TEMPERATURE TRANSMITTER - OPERATING MANUAL – V1.0x H
INTRODUCTION
TxRail-USB is an USB configurable DIN rail mount temperature
transmitter. It allows selection and configuration of input type,
measurement range, output type and calibration. Its output can be
set to either loop powered 4-20 mA or 0-10 Vdc. Highly accurate and
user-friendly, the TxRail-USB performs well from simple to
sophisticated measurement applications.
The output current is linearized according to the selected input
sensor and adjusted to the configured range.
SPECIFICATIONS
Sensor input: User defined. The supported sensors are listed in
Table 1, along with their maximum ranges.
Thermocouples: Types J, K, R, S, T, N, E and B, according to
IEC 60584 (ITS-90). Impedance >> 1 MΩ
Pt100: Type 3-wire, Excitation 0.8 mA, α= 0.00385, according
IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
Pt1000: Type 3-wire, Excitation 0.8 mA, α= 0.00385, according
IEC 60751 (ITS-90).
For 2-wire sensors, tie terminals 3 and 4 together.
NTC R
: 10 kΩ ±1 %, B
25°C
25/85
Voltage: 0 to 50 mVdc. Impedance >> 1 MΩ
Maximum Measurement
Sensor Type
Range
Voltage
0 to 50 mV
K
-150 to 1370 °C
Thermocouple
J
-100 to 760 °C
Thermocouple
R
-50 to 1760 °C
Thermocouple
S
-50 to 1760 °C
Thermocouple
T
-160 to 400 °C
Thermocouple
N
-270 to 1300 °C
Thermocouple
E
-90 to 720 °C
Thermocouple
B
500 to 1820 °C
Thermocouple
Pt100
-200 to 650 °C
Pt1000
-200 to 650 °C
NTC
-30 to 120°C
Table 1 – Sensors accepted by the transmitter
Switch-on delay: < 2.5 s. The accuracy is only guaranteed after 15 min.
Terms of reference: ambient: 25 ° C; voltage: 24 Vdc, load: 250 Ω;
settling time: 10 minutes
Temperature Effect: < ±0.16 % / 25 °C
Response time: typical 1.6 s.
Maximum voltage allowed at input terminals no sensor: 3 V.
RTD current: 800 µA.
RTD cable resistance effect: 0.005 °C /
Maximum allowable cable resistance for RTD: 25
NOVUS AUTOMATION
= 3435
Minimum Measurement
Range
5 mV
100 °C
100 °C
400 °C
400 °C
100 °C
100 °C
100 °C
400 °C
40 °C
40 °C
40 °C
.
Sensor Type
Pt100 / Pt1000
(-150 to 400°C)
Pt100 / Pt1000
(-200 to 650°C)
mV, K, J, T, E, N, R, S, B
NTC
Table 2 – Calibration error, percentage of the full measurement range.
(*) Add cold junction compensation: < ± 1 °C.
Power supply influence: 0.006 % / V typical (percentage of the full
measure range).
Output (4-20 mA): 4-20 mA or 20-4 mA current, 2-wired; linearized
according to the selected sensor.
Output Resolution (4-20 mA): 2 µA.
Output (0-10 Vdc): 0-10 Vdc or 10-0 Vdc voltage, linear with respect
to the measured temperature for the selected sensor.
Output Resolution (0-10 Vdc): 0.0025 V (12 bits)
Power supply: 10 to 35 Vdc (output 4-20 mA) and
12 to 35 Vdc (output 0-10 Vdc).
Maximum load (RL): RL (máx.) = (Vdc – 10) / 0.02 [Ω]
Where: Vdc= Power supply voltage (10-35 Vdc)
Operating Temperature: -40 to 85 °C
Humidity: 0 to 90 % RH
Electromagnetic Compatibility: EN 61326-1:2006
No electrical isolation between input and output.
Internal protection against polarity inversion.
Cold junction compensation for thermocouples.
Connection Wire Cross Section: 0.14 a 1.5 mm²
Screw Tightening: 0.8 Nm.
Housing: ABS UL94-HB.
Certification: CE
CONFIGURATION
Changes to the configuration are possible through the TxConfig II
software, provided free of charge.
A TxRail-USB Setup Kit consisting of the TxConfig II software and
USB cable can be purchased from the manufacturer or any authorized
distributor. The TxConfig II software is continuously updated and new
versions can be downloaded at no charge from the manufacturer's
website. To install, execute the TxConfigIISetup.exe file and follow the
instructions.
Typical
Maximum
Accuracy
Accuracy
0.10%
0.12%
0.13%
0.19%
*
*
0.1 % (
)
0.15 % (
)
0.3 °C
0.7 °C
1/4

Advertisement

loading
Need help?

Need help?

Do you have a question about the TxRail-USB and is the answer not in the manual?

Questions and answers

Summary of Contents for Novus TxRail-USB

  • Page 1 Table 1 – Sensors accepted by the transmitter A TxRail-USB Setup Kit consisting of the TxConfig II software and Switch-on delay: < 2.5 s. The accuracy is only guaranteed after 15 min. USB cable can be purchased from the manufacturer or any authorized Terms of reference: ambient: 25 °...
  • Page 2: Mechanical Installation

    MECHANICAL INSTALLATION SOFTWARE CONFIGURATION: The TxRail-USB transmitter is suitable to be installed in heads. Vibrations, moisture and extreme temperatures, electro-magnetic interference, high voltage and other interferences can permanently damage the unit, and could cause error in the measured value.
  • Page 3: Electrical Installation

    TxRail-USB OPENING THE TRANSMITTER: PT100 3-WIRE In order to open the transmitter, you must press the orange lockers located on both sides of the enclosure and pull the frontal cover very carefully, just like shown in Fig. 05. Fig. 7 – Transmitter electrical connections (Pt100 3-wire) PT100 4-WIRE Fig.
  • Page 4 TxRail-USB OUTPUTS (0-10 V and 4-20 mA) Fig. 11 – Transmitter electrical connections (0-10 V and 4-20 mA) OPERATION The sensor offset can be changed through the TxConfig II software. The USB cable may be connected to the transmitter without causing any measurement errors.