Installation and Operating Specification SA-5 10

5 Electrical installation

5.1 EMC-compatible installation of control lines

Pay attention to maintain sufficient distance from powerlines and
motor wires to prevent interferences.
When using a shielded cable the shield must be connected (as
short and with as low an induction as possible!) to the PE conduc-
tor on one side at the signal input (of the evaluation unit).

5.2 Connection Voltage supply

Connection Voltage supply at terminals: "10 V" and "GND". Here, it
must be strictly observed that the mains voltage lies within the
allowable tolerance specifications ( Technical data and name-
plate affixed to the side).
Danger due to electric current
Only PELV current sources which ensure safe electrical isolation
of the operating voltage in accordance with IEC/DIN EN 60204-1
must be used.
There is no potential isolation between supply voltage and output
signal.

5.3 Output voltage 0 - 10 V

Connection to terminals "A" and "GND" (I
Information
The output voltage is directly dependent on the supply voltage!
It is not permissible to connect outputs of several devices to
each other!
There is no potential isolation between supply voltage and
output signal.
In the as-delivered state, the following output voltages are as-
signed to the selectable steps:
L-BAL-E328-GB 2023/33 Index 002
max
Part.-No.
8/14
Electrical installation
Technical data).