Installation and Operating Specification SA-5 10
5 Electrical installation
5.1 EMC-compatible installation of control lines
Pay attention to maintain sufficient distance from powerlines and
motor wires to prevent interferences.
When using a shielded cable the shield must be connected (as
short and with as low an induction as possible!) to the PE conduc-
tor on one side at the signal input (of the evaluation unit).
5.2 Connection Voltage supply
Connection Voltage supply at terminals: "10 V" and "GND". Here, it
must be strictly observed that the mains voltage lies within the
allowable tolerance specifications ( Technical data and name-
plate affixed to the side).
Danger due to electric current
Only PELV current sources which ensure safe electrical isolation
of the operating voltage in accordance with IEC/DIN EN 60204-1
must be used.
There is no potential isolation between supply voltage and output
signal.
5.3 Output voltage 0 - 10 V
Connection to terminals "A" and "GND" (I
Information
The output voltage is directly dependent on the supply voltage!
•
It is not permissible to connect outputs of several devices to
•
each other!
There is no potential isolation between supply voltage and
•
output signal.
In the as-delivered state, the following output voltages are as-
signed to the selectable steps:
L-BAL-E328-GB 2023/33 Index 002
max
Part.-No.
8/14
Electrical installation
Technical data).