Klein Tools RT210 - GFCI Receptacle Tester Manual

Klein Tools RT210 - GFCI Receptacle Tester Manual

Also See for RT210:

Advertisement

Klein Tools RT210 - GFCI Receptacle Tester Manual

INDICATORS

INDICATORS

GENERAL SPECIFICATIONS

Relative Humidity: < 85% non-condensing
Operating Temperature: 32° to 140°F (0° to 40°C)
Storage Temperature: 14° to 122°F (-10°C to 50°C)
Operating Altitude: Up to 6562 ft. (2000 m)
Weight: 1.2 oz. (33 g)
Nominal Voltage: 110 - 125V AC at 50/60Hz in 3-wire outlet
Mains supply voltage fluctuations: ±10%
Pollution Degree: 2
Nominal Power: 0.3W
Standarts: Conforms To UL Std 61010-1, 61010-2-030,1436
Certified To CSA Std C22.2 #61010-1, 61010-2-030,160 5001748
Drop Protection: 6.6 ft. (2 m)
Safety Rating: CAT II 300V


Read, understand, and follow all warnings and instructions before operating testers. Failure to follow instructions could result in death or serious injury. Before each use, verify tester operation by testing on a known live and correctly wired receptacle. Do not use if the tester appears damaged in any way. The tester is intended for indoor use only. Other equipment or devices attached to the circuit being tested could interfere with the tester, clear the circuit before testing. This tester only detects common wiring problems. Always consult a qualified electrician to resolve wiring problems.

WIRING CONFIGURATION TESTING

Conditions indicated: wiring correct, open ground, reverse polarity, open hot, open neutral and hot/ground reversed.

Conditions NOT indicated: quality of ground, multiple hot wires, combinations of defects, reversal of grounded and grounding conductors.

All appliances or equipment on the circuit being tested should be unplugged to help reduce the possibility of erroneous readings.

STANDARD RECEPTACLES

  1. Verify tester operation by testing on a known live and correctly wired receptacle.
  2. Plug tester into receptacle.
  3. Compare the illuminated lights on the tester to the key code printed on the tester.
  4. If the tester indicates that the receptacle is not wired correctly, consult a qualified electrician.

GFCI RECEPTACLES

  1. Check the GFCI receptacle user manual for information on how the specific receptacle operates prior to using this tester.
  2. Insert the tester into the receptacle under test to check for correct wiring (See FIG. 1). Lights on the tester should illuminate.
  3. Press the "TEST" button on the GFCI receptacle. Did the GFCI trip and the lights on the tester go dark? YES: Reset the GFCI by pressing the reset button. Proceed to step 4. NO: The GFCI is not operating properly or the receptacle is miswired. Consult a qualified electrician.
  4. Press and hold the test button on the tester for 7 seconds. Did the GFCI trip and the lights on the tester go dark? YES: Reset the GFCI by pressing the reset button. The GFCI appears to be operating properly. NO: The GFCI is not operating properly or the receptacle is miswired. Consult a qualified electrician.

CLEANING

Wipe with a clean, dry lint-free cloth. Do not use abrasive cleaners or solvents.

DISPOSAL / RECYCLE

Do not place equipment and its accessories in the trash. Items must be properly disposed of in accordance with local regulations. Please see www.epa.gov or www.erecycle.org for additional information.

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Klein Tools RT210 - GFCI Receptacle Tester Manual

Advertisement

Need Assistance?

Do you have a question about the RT210 that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents