Remove the wall plate and flip open the Master button open as shown...
1. Press the SMARTWIRE tab as shown in Figure 6.
The LED next to the tab will flash once, then the individual button LEDs will begin to flash ON/OFF.
2. Press the switch button you want to smartwire (Master button on an HDLS1SS-x).
The LED for that button continues to flash; LEDs for the other buttons will stop flashing.
LEDs for the relays currently controlled by that switch button will also begin to flash.
The HCLK8SS clock/programmer, AA-BASE Automation Appliance and WinControl software can also
program Dataline Switches. Refer to the corrsponding operation guide for the programming options
supplied with your system.
3. Select the relays to be controlled.
In the relay panel, press the associated relay control button to add/delete that relay to/from the group.
To smartwire a dataline switch to a Channel, press the channel button instead of the relay control
button.
4. Press the SMARTWIRE tab again.
All LEDs will stop flashing.The selected switch button will now control the selected group of relays.
Press the switch button you want to smartwire (Master button on an HDLS1SS-x). The LED for that
button continues to flash; LEDs for the other buttons will stop flashing. LEDs for the relays currently
controlled by that switch button will also begin to flash.
Press the selected switch button again to toggle the relay group ON/OFF/ON. Now press each relay
control button to turn the relay OFF. The switch button LED will go from red (all relays on) to green (mixed
group) to OFF when the last relay in the group is turned OFF.
Any dataline switch may be configured as either an ON/OFF Group Switch or a Pattern Switch. The
Patterns mode allows the group of relays to be forced to a combination of ON/OFF states to provide a
lighting "scene." For more information on Patterns, refer to Special
Functions.
Smartwiring a Dataline Switch in Patterns mode is similar to the
procedure described in Figure 6, with one additional step:
1. Press the SMARTWIRE tab.
2. Press the Switch button.
3. Press the PATTERNS button on the Group Switching card in the
panel.
4. Press the relay control button to change the relay LED's status.
Select relay status as follows:
• LED Red: Relay is IN the group and turns ON with switch button
press.
• LED Green: Relay is IN the group but forced OFF with switch
button press.
• LED Off: Relay is NOT IN the group.
5. Press the SMARTWIRE tab again.
Units are supplied with 2 sets of button caps. One set is solid plastic and suitable for engraving (contact the Factory for custom
engraving). The second set of button caps will accept user-supplied labels.
The individual switch buttons provide space for 3/8" wide x 11/16" long (9mm x 30mm) label directories. The labels can be attached
simply by removing the clear lenses, positioning the labels and replacing the lenses as shown at right.
If desired, the buttons may be completely removed from the base plate and labeled separately. You may find this method easier to
achieve better alignment of the labels.
To remove a button from a 1-, 2- or 4-button switch, gently lift and rotate it around until it snaps free of the hinge bracket. To replace the
button, press the hinge pin into the hinge bracket until it snaps in place.
Removing buttons from an 8-button switch is slightly different. With your small screwdriver, pry the hinge end of the button free from the
hinge bracket. Lift the button out, twisting it slightly, if necessary, to free the small hook holding the center edge of the button in place. To
replace the button, position the small center hook in place and press the hinge pin into the hinge bracket until it snaps in place.
TEST
PATTERNS OR 'SCENES'
SWITCH BUTTON LABELING
Pattern LED indicator
R
R
R
B
B
B
Y
Y
Y
W
W
W
D
Pattern push-button
4
Figure 6 – Smartwiring a
Dataline Switch
1
PRESS SMARTWIRE TAB ONCE
SMARTWIRE LED FLASHES ONCE
ALL SWITCH BUTTON LEDS
BEGIN FLASHING
SMARTWIRE
2
PRESS SWITCH BUTTON TO BE
PROGRAMMED
SELECTED BUTTON LED
CONTINUES TO FLASH
OTHER LEDS STOP FLASHING
SMARTWIRE
3
PRESS RELAY CONTROL BUTTON TO
ADD OR DELETE FROM THE GROUP
4
PRESS SMARTWIRE TAB AGAIN
ALL LEDS STOP FLASHING
E
SMARTWIRE
SMARTWIRE
LED
FLASHING
LED
RELAY
CONTROL
BUTTON

Advertisement

loading

This manual is also suitable for:

Wattstopper hdls2ssWattstopper hdls4ssWattstopper hdls8ss