LEGRAND Wattstopper HDLS1SS Manual page 3

Lighting integrator dataline switch

Advertisement

Lighting Integrator Panel
(01) First Floor
Panels numbered
(01) sequentially (02)
Relays
Automation Card
Dual twisted pair
(use both pairs of
HDL W4P for
local dataline)
Dataline Switches
01-01
Single twisted pair data communications, max. length 1500'
(use one pair of HDL W4P for global dataline)
Lighting Integrator Panel
(10) Basement
Automation Card
Figure 3 – Dataline Switch Numbering
Figure 4 – Dataline Switch Documentation Form
MANUAL SMARTWIRING OF A DATALINE SWITCH TO A RELAY GROUP
Dataline switches are typically wired to a single relay or group of relays within a panel. Wiring to a channel
provides a simple way of manually overriding all of the relays that are grouped to an automation channel
(A-P) within a panel.
For systems using the AA-Base (Automation Appliance) as the primary programming and scheduling device,
use only the user interface provided by the AA-Base (web browser) to smartwire the HDLS Dataline switch
buttons. Manual smartwiring will be automatically overridden by the programming in the AA-Base. See the
AA-Base documentation for additional information on programming HDLS Dataline switches.
When using HDLS switches with WinControl software, the Smartwire feature must be enabled in the
software.
Lighting Integrator Panel
(02) Second Floor
Switch Buttons
(#1 at top)
01-02
01-03
Dual twisted pair (use both pairs
of HDL W4P for local dataline)
Dataline Switches
...
10-01
10-02
10-63
MAXIMUM TOTAL NUMBER OF DATALINE DEVICES IS 63 PER PANEL.
MAXIMUM TOTAL LENGTH OF LOCAL DATALINE WIRE IS 1500 FEET.
Automation Card
Dual twisted pair
(use both pairs of
HDL W4P for
local dataline)
Dataline Switches
...
02-01
02-02
02-63
Dataline Switches for each
panel numbered sequentially
(Panel # - Switch #)
Other panels
3
Figure 5 – Switch ID Label
Panel#