Controller overall,
Start-up
LED feed back
Default factory
settings
18
continued
When power is connected, the controller boots up that last up to 120 seconds, in which
the unit seems to be total off.
After 120 second the fans starts and control LED turn on, and the system is running.
The PCB board has two LED located above the SD card reader close to the PCB board
edge.
Green LED is lit in normal operation.(120 seconds initialising time, after re-
boot)
RED LED is lit, if any of the alarms states are active on any of the outputs. The
power save mode alarm will stop normal operation; any other alarm doesn't af-
fect the operation.
By default the Flexibox is delivered with standard parameters that is setup:
No AC connected. To be changed in parameter Please consult the CC4 manual
for further information
Digital input set as fire shut down. When input is activated, the fan shuts down,
and any motorized damper will close. Input 1 has higher priority than input 2.
See more at page 27
Critical operation alarms are active on output 1, and maintenance warnings (fil-
ter change) are active on output 2. See more at page 26