EXTERNAL VIEWS

■ FRONT VIEW (with the cover open)
Power LED
Status Indicator LED
Configurator Jack
INPUT/OUTPUT RANGING
The internal DIP switch setting is required to select input
and output types before setting a precise range using PC
Configurator Software (model: M6CFG).
For detailed information on the PC configuration, refer to
the M6CFG users manual.
Table 1. DIP switch setting: Input type
Input Type
SW2-1
0 – 50 mA
-1000 – +1000 mV
-10 – +10 V
Table 2. DIP switch setting: Output type
Output
Type
1
2
3
0 – 20 mA*
ON
ON OFF OFF OFF OFF ON OFF
1
-5 – +5 V
OFF OFF ON OFF ON OFF OFF ON
-10 – +10 V
OFF OFF ON OFF OFF ON OFF ON
*1. For 0 – 1 mA range, set switches as in the table below.
Output
Range
1
2
3
0 – 1 mA
OFF OFF ON OFF OFF OFF ON OFF
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Confirm that the wire insulation tubes are not caught in
the clamp.
3) Check DIP switch setting.
4) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
5) Input: Check that the input signal is within 0 – 100% of
the full-scale.
6) Output: Check that the load resistance meets the de-
scribed specifications.
■ SIDE VIEW
ON
OFF
OFF
SW1
4
5
6
7
SW1
4
5
6
7
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
5
6
7
8
1
2
3
4
STATUS INDICATOR LED
The transmitter is provided with a status indicator LED
which blinks in different patterns indicating various oper-
ating status.
The following figure indicates typical patterns.
TRANSMITTER STATUS
Normal operating
mode
Abnormal operating mode

MAINTENANCE

Regular calibration procedure is explained below:
8
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal while the control input is
TRACK. Check that the output signal for the respective
input signal remains within accuracy described in the data
sheet. When the output is out of tolerance, recalibrate the
unit using the PC Configurator Software (model: M6CFG).
8
LIGHTNING SURGE PROTECTION
M-System offers a series of lightning surge protector for
protection against induced lightning surges. Please contact
M-System to choose appropriate models.
Output Range Selectors
Input Range Selectors
LED ON-OFF PATTERNS
Hold
Track
80 milliseconds
ON
EM-7990 Rev.3 P. 4 / 5