START AND STOP

Check daily
NOTE
Do not alter the primary conditions of regulation
and do not touch the sealed parts.
The starting of the unit can be effected in 3 different
modes:
1) Start with EP6 key (Engine Control)
Put the "Local/Remote" selector on Local. Turn
the key on "ON", the EP6 display shows only on
the machines with mounted glow plugs for 5 secs,
the symbol "UUUU", then the message "Sta"
appears the engine can be started, for which turn
the key on "start" and start the engine.
On the display the word "Sta" remains for about
20 secs then automatically disappears; the engine
must be started within 20 secs, otherwise the
EP6 blocks the starting and on the display the
word "fail" appears. Turning the key on "OFF" the
EP6 is reset and a new starting cycle can be
fixed.
Stop:
it is COMPULSORY to disconnect the load first,
then to stop the engine turn the key on "OFF".
2) Remote starting with TCM35
Put the "Local/Remote" selector on Local.
Connect TCM35 to the plug on the front panel
and put the switch on "0".
Turn the key on ON in the EP6 (Engine Control),
wait for the various signals to go out then press
the button "AUTO" in the EP6 until the led "AUTO"
flashes.
Shift the switch on "I" in the TCM35 and
automatically the starting cycle will start. On the
machines with mounted glow plugs appears in
the display EP6 (for about 5 secs), the symbol
"UUUU"; the starting cycle includes 3 starting
trials.
When the engine starts the led "AUTO" remains
lit continuously and simultaneously the red warning
light will light in the TCM35.
Stop:
it is COMPULSORY to disconnect the load first,
then shift the switch of the TCM35 on "0", the
engine will stop immediately.
GE 14000 YS/GS
GE 20-55-65 PS/PSX
GE 35 PS - GE 85-115 PSX
3) Start with Automatic start unit (EAS)
Put the "Local/Remote" selector on Remote.
Connect the EAS to unit.
The EAS controls the starting as well as the stop
of the engine.
Follow attentively the instructions reported in the
EAS manual. In these conditions the EP6 has the
only function to measure the electric values, hour-
meter, etc.
CAUTION
MACHINE WITH EMERGENCY BUTTON
Pressing the button the engine will stop
immediately in any working condition.
Turn clockwise to reset the button.
CAUTION
RUNNING-IN
During the first 50 hours of operation, do not use
more than 60% of the maximum output power of
the unit and check the oil level frequently, in any
case please stick to the rules given in the engine
use manual.
NOTE
For safety reason the key must be kept by
qualified personel.