Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)
1
Fasten the chassis to the front of the rack with two
12-24 or 10-32 screws on each side.
2
Front-mount bracket.
d) Tighten the 10-32 screws to 20 in-lb (2.26 N·m) or tighten the 12-24 screws to 30 in-lb (3.39 N·m).
Step 6
If you attached a grounding wire to the chassis grounding pad, connect the other end of the wire to the facility ground.
Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)
The airflow sleeve (N9K-AIRFLOW-SLV) is installed to allow proper airflow, so that the switch is properly
cooled. This airflow sleeve is only compatible with rack mount kit (N3K-C3064-ACC-KIT).
Table 3: Airflow Sleeve (N9K-AIRFLOW-SLV) Minimum and Maximum Rack Rail Depth.
Chassis
N9K-C92348GC-X
N9K-C9316D-GX
N9K-C9332C
N9K-C9332D-GX2B
N9K-C9336C-FX2
Cisco Nexus 93180YC-FX3 ACI-Mode Switch Hardware Installation Guide
26
3
Mounting rails on rack or cabinet posts.
Minimum Rack Depth
636.49 mm
824.80 mm
794.20 mm
824.00 mm
802.39 mm
Installing the Switch Chassis
Maximum Rack Depth
748.25 mm
916.60 mm
898.70 mm
915.80 mm
903.98 mm