Installing The Airflow Sleeve (N9K-Airflow-Slv) - Cisco Nexus 93108TC-FX3P Hardware Installation Manual

Aci-mode switch
Hide thumbs Also See for Nexus 93108TC-FX3P:
Table of Contents

Advertisement

Installing the Switch Chassis

Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)

The airflow sleeve (N9K-AIRFLOW-SLV) is installed to allow proper airflow, so that the switch is properly
cooled. This airflow sleeve is only compatible with rack mount kit (N3K-C3064-ACC-KIT).
Table 2: Airflow Sleeve (N9K-AIRFLOW-SLV) Minimum and Maximum Rack Rail Depth.
Chassis
N9K-C92348GC-X
N9K-C9316D-GX
N9K-C9332C
N9K-C9332D-GX2B
N9K-C9336C-FX2
N9K-C9336C-FX2-E
N9K-C9348GC-FXP
N9K-C93108TC-FX
N9K-C93108TC-FX3P
N9K-C93180YC-FX
N9K-C93180YC-FX3
N9K-C93180YC-FX3S
N9K-C93600CD-GX
Note
Before you begin
• Verify that your shipment is complete.
• Install your rack in a secure location.
Insert the airflow sleeve into the rack and attach it as follows:
a) Holding the airflow sleeve (N9K-AIRFLOW-SLV) with both hands, position it in front of the fan side of the chassis.
b) Holding the airflow sleeve level, insert screws (12-24 or 10-32, depending on the rack type) in each of the two front
rack-mount flanges (using a total of two screws) and into the cage nuts or threaded holes in the vertical rack-mounting
rails (see the following figure).
You supply the screws to mount the airflow sleeve.
Cisco Nexus 93108TC-FX3P ACI-Mode Switch Hardware Installation Guide
Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)
Minimum Rack Depth
636.49 mm
824.80 mm
794.20 mm
824.00 mm
802.39 mm
806.90 mm
672.49 mm
781.29 mm
672.49 mm
781.29 mm
672.49 mm
672.49 mm
824.80 mm
Maximum Rack Depth
748.25 mm
916.60 mm
898.70 mm
915.80 mm
903.98 mm
898.70 mm
764.29 mm
873.09 mm
769.69 mm
873.09 mm
784.25 mm
784.25 mm
916.60 mm
23