Download Print this page

Grundfos CRE Safety Instructions And Other Important Information page 16

E-pumps with mge model k motor

Advertisement

14.1.3.2 Ambient temperature during operation
Model K
Description
Minimum
Maximum
13)
26 kW MGE motors are rated for a maximum value of
40 °C.
14.1.4 Humidity
Description
Maximum humidity (non-condensing)
If the humidity is constantly high and above 85 %,
open the drain holes in the drive-end flange to vent
the motor.
If you install the motor in moist
surroundings or areas with high humidity,
ensure that the bottom drain hole is open.
As a result, the motor becomes self-
venting, allowing water and humid air to
escape. When you open the drain hole,
the enclosure class of the motor will be
lower than standard.
14.1.5 Pollution degree
The product is approved for Pollution degree 3 rating.
14.2 Technical data, three-phase motors
WARNING
Electric shock
Death or serious personal injury
Use the recommended fuse size.
Supply voltage
3 × 380-480 V -10 % / +10 %, 50/60 Hz, PE
3 × 400-480 V -10 % / +10 %, 50/60 Hz, PE
3 × 380-480 V, 50/60 Hz, Model K
Speed
[rpm]
1450-2200
2900-4000
16
3 × 380-480 V
-20 °C
50 °C
13)
Percentage
95 %
Power
Mains voltage
[kW]
[V]
≤ 400
11-22
> 400
≤ 400
15-22
> 400
Check that the supply voltage and frequency
correspond to the values stated on the nameplate.
Recommended size of fuse
For recommended size of fuses see the tables below.
3 × 380-480 V, Model K
Motor size
Recommended
[kW]
[A]
11
35
15
50
18.5
60
22
70
3 x 400-480 V, Model K
Recomme
Motor size
nded
[kW]
[A]
26
80
For recommended size of fuses see the
appendix concerning installation in the
USA and Canada.
14.2.1 Leakage current (AC)
The leakage currents are measured without any load
on the shaft and in accordance with EN
61800-5-1:2007.
WARNING
Electric shock
Death or serious personal injury
If the leakage current is greater than
3.5 mA, use a PE cable with a
minimum cross-section of at least 10
2
mm
, or use 2 separate PE cables with
the same cross section as the power
cable.
Leakage current (I
Maximum
Fuse
type
[A]
63
gG
80
gG
80
gG
80
gG
Maximum
Fuse type
[A]
80
gG
)
L
[mA]
3.5 < I
< 20
L
3.5 < I
< 30
L
3.5 < I
< 20
L
3.5 < I
< 30
L

Advertisement

loading

This manual is also suitable for:

CrieCrneSpkeMtreBms