6 Compliance Information
6.1 UUCUL Compliance
6.1.1 Residential Listings (US and Canada)
When installed following the guidelines presented below, the
BHS-4000A system is compliant with these agency listings:
UL 985 ~ Household Fire Warning System Units
UL 1023 - Household Burglar Alarm System Units
UL 1635 - Digital Alarm Communicator system Units
UL 1637 - Home Health Care Signaling Equipment
The system also complies with the following Canadian listings:
CAN/CUL-S545-M89 - Standard for Residential Fire
Warning System Control Units
UL 1023 - Household Burglar Alarm System Units
6.1.2 Hardware Guidelines
Use only UL listed devices.
Use recognized limited energy cables.
Do not plug the transformer into a receptacle that is
controlled by a switch. Use an approved transformer from
the list below (according to location of installation):
Note: Part Numbers in italics = w/Ground Terminal
US
Canada
_(UL Listed)
(UL/CSA Listed)
Basler_
16.5V 25VA
BE116225CAA0002
BE116225AAA0024
16.5V 25VA
BE116225CAA0001
__
16.5V 40VA
BE 156240CAA00Q7_
UitraTech____ .
16.5V 40VA
IM-16V 40VA
_
IM-16V40VA
_
16.5V 40VA
E-HWAT16V40
E-HWAT16V40
_
ELK___
16.5V 40VA
TRG1640
__
Universal_______
16.5VAC 40VA UB1640W_
16.5VAC 25VA UB1625B/US2
_
16.5VAC 25VA
UB1625B/US3
_
UB1625B/CA3
Revere
16.5VAC40VA lRT-1640
Use one of the 12 VDC batteries listed below:
"Premier 12VDC4Ah
IPT1245
Power Sonic 12VDC 5Ah_PS1250__
Power Sonic 12VDC 7Ah
PS1270
Universal Battery 12VDC 7Ah_ UB1270_
Universal Battery 12VDC 4.5Ah_
UB1245 _
Yuasa 12VDC 4Ah
NP4-12
Yuasa 12VDC 7Ah
[NP7-12
Battery backup requirement: Residential Fire (US &
Canada), Home Health Care = 24 hour w/ 4 minute alarm
time.
Battery backup requirement: Residential Burglary (US &
Canada) Commercial Burglary and DACT = 4 hour w/5-15
minute alarm time.
Use Premier or Universal PTS-15 BHSW Range 4-16 Ohm
speaker across the SIREN and Common terminals for
Residential Fire and Burglary applications. For Canadian
Residential Fire, use the Amseco MSB Series 12VDC bell. In
a Multi Area system, these devices must be placed so that it
can be heard in all areas as they are the primary sounding
devices. The sounder on the 2112ATL smoke detector is a
supplementary sounding device.
Fire zones must use System Sensor Model 2112ATL smoke
detector, ADEMCO 5808LST wireless smoke detector or
other UL Listed 4-wire Smoke Detector with EOL Relay.
Use the IntelliSense/Honeywell 9.X 4.7 K EOL resistors for all
hardwired fire zones.
Use 4.7K Ohm end-of-line resistors on all burglary zones.
Do not exceed the maximum combined auxiliary, fire and
keypad current (1.0A for a 25VA or 1 2A with a 40VA
transformer, including alarm outputs).
Do not exceed the maximum current draw for the Bell output
(1 A). The primary sounding output device should be a siren
for residential systems or a bell for commercial systems.
Install the keypads within the protected area. If mounted
outside of protected areas, keypads must be set up for
tamper protection.
Use SIA format with Silent Knight 9800 Receiver.
Note: The Keyfob, Keyfob Receiver, BHS-3420, and Virtual
Keypad have not been investigated by Underwriters Laboratories,
Inc.
.
6.1.3 Programming Guidelines
To ensure that the BHS-4000A system
is compliant with the
Listings in Section 6.1.1 . program the system as follows:
The MOS Suspend mode is not to be used in UL Certified
installations.
Program each keypad's exit delay to be 120 seconds or less.
(Standard Menu | Set Exit Delay)
Program each entry delay for 45 seconds or less.
(Advanced Menu | Account | Area | Zone | Vw/Edt Zone |
Entry Delay Time)
Program each Entry/Exit Zone
individually.
User Codes must be at least 3 digits long (Advanced Menu
| Account | Vw/Edt Acnt | User Code Length).
Siren Supervision must be enabled when using the siren
output.
Program all burglary sounding devices to operate for at least 4
minutes. (Advanced Menu | Device | Vw/Edt Device 01 Alarm
outputs | Burglary Cutoff)
Set Medical Cutoff Time to a
minimum of 5 minutes for Home Health Care applications
.
Burglary zones must be programmed as EOL and the Alarm
output cadence must be steady.
Fire zones (both hardwire and soft zones) must be programmed
as supervised, with Temp Code 3 (USA or CAN) alarm
cadence.
Medical zones must be programmed for silent or a pulsing
cadence.
No zone may be programmed for silent alarm.
Do not program the panel to dial a police station.
Do not program the panel to dial an emergency, police
station, or fire alarm number.
Program the fire alarm time-out for manual shutdown.
(Advanced Menu | Device | Vw/Edt Device 0 [ Alarm
outputs | Fire Cutoff; program 0.)
Program the dialing attempts for Comms 1 and 2 to be at
least 5, and no more than 10. (Advanced Menu | Comm |
Vw/Edt Comm | Dial Attempts)
Program the test message interval to once every 24 hours.
(Advanced Menu | Account | Vw/Edt Acnt | Test Interval
Hrs) In a multiple area system, it is only necessary to send
the test interval on one of the area accounts since they
share the same dialer.
Program the panel to report all fire trouble conditions to the
central station. (Advanced Menu | Comm | Vw/Edt Comm |
Fire Trouble; program "yes" for Communicator 1.)
Enable AC and Battery trouble reporting. (Advanced Menu |
Comm Vw/Edt Comm | AC Fail;
and
Advanced Menu |
Comm Vw/Edt Comm j Low Battery; program both as
"yes" for Communicator 1.)
Pager reporting can only be used as a supplementary
method, primary reporting must be to a central station.
17