Berker 8536 52 00 Operating Instructions
Berker 8536 52 00 Operating Instructions

Berker 8536 52 00 Operating Instructions

Knx-rf controller 220 solar

Advertisement

Quick Links

IP55
z
Operation instructions
KNX-RF controller 220° solar
+ 90°/- 30°
Order no.
8536 52 00
+/-80°
Description
IP55
Vertical adjustment
Wall fixing plate
+/-80°
Detection zone
m 16
m 4
m 2,5
IP 5 5
m 0,5
m 8
m 16
Optimal installation height is 2.5m.
The detection zone shall remain free of obstacle.
Installation
2,5 m
01
Adjustments
Delay
Brightness
(lighting time)
+ 90°/- 30°
Adjustment potentiometers
Directional detection head
LED A
Shutters
1
Angle fixing support 8590 02 00
Caution :
- This device must be installed only by
a qualified electrician according to the
installation standards in force in the
country.
Product Description and working
principles
This detector allows remotely control of one
or more receivers for a given time when a
movement is detected in its detection zone.
cfg
This product can be used in two types of
configuration: one detector controls one/seve-
ral receiver(s); several transmitters control the
receiver(s).

Operation

The receiver(s) is(are) under control as soon
as the brightness level as set by potentiometer
Sensitivity
is considered too low and a movement is
2
level
(change
detected.
of range)
Upon detection, the time delay is restarted.
If LED A flashes quickly during configuration,
the position of potentiometer
tible with the selected function.
Product factory reset is recommended before
version à pile
any new configuration.

Factory reset

Keep push-button
depressed until LED
J
cfg flashes (>10s), and then release it.
LED cfg is turned off when factory return is
completed.
After factory return, wait 15 s before starting
configuration.
LED B
Action
Adjustments
Use Auto (factory)

Auto Settings

settings to set
Put the Lux potentiometer on
automatic lighting
"auto test".
turn-on for
The settings are predefined :
a given time.
Lux =
Only available when
(operating at night only)
a detector's time
time = 3 min,
delay is set.
sensitivity = max
Turn automatic

Installer settings

lighting on for
2
a given time.
Only available when
a detector's time
delay is set.
ech40%
Adjust sensitivity.
Allows setting the range
to avoid disturbance.
6LE003100C
02
Button
J
LED cfg
Button
J
cfg
Configuration (button
)
J
These detectors can be configured in 3 different
ways :
• quicklink& : configuration without tool, directly
on the device via
button and LED (see confi-
J
guration instructions quicklink& ).
• tebis TX: configuration using connection device
1
is not compa-
from Hager
• ETS3/ETS4 via KNX-RF/TP gateway: database
and description of application software available
version solaire
from the manufacturer.
Configuration by ETS
Press
button for addressing by means of radio/
J
KNX gateway.
Product factory reset is required to change
O
the configuration mode.
cfg
Potentiometer
,
Test and validation of detection
zone
Set potentiometer
2
to mode "auto test".
The test mode is available only once the
O
product has been configured.
The Test mode is available for 3 minutes time
and does not take brightness level into
account.
Each detected movement turns LED A on for
2 seconds.
The associated receiver is controlled.
After 3 minutes without detection, the product
is set back to auto mode.

Limitation of detection zone :

You can limit the detection zone using the
shutters supplied or by inclining the head.

Mounting

Projection or ceiling mount :
- Fix the wall plate using the supplied screws.
- Clip the detector onto the wall plate
- Tighten the screws to close.
For angle mounting, the wall fixing plate is
fitted between the accessory and
the detector.

Precautions for installation

For optimum detection conditions, please fol-
low these recommendations :
- Keep the detector protected from bad
weather, as it is sensitive to these conditions.
- Maintain 1m distance between the light
source and the detector and keep the detec-
tor out of the light source.

Correct Disposal of This product

(Waste Electrical & Electronic
Equipment).
(Applicable in the European Union and other European
countries with separate collection systems).
This marking shown on the product or its literature
indicates that it hould not be disposed with other
household wasted at the end of its working life. To
prevent possible harm to the environment or human
health from uncontrolled waste disposal, please
separate this from other types of wastes and recycle it
responsibly to promote the sustainable reuse of
material resources.
Household users should contact either the retailer
where they purchased this product, or their local
government office, for details of where and how they
can take this item for environmentally safe recycling.
Business users should contact their supplier and
check the terms and conditions of the purchase
contract. This product should not be mixed with other
commercial wastes of disposal.
å
Usable throughout Europe
and in Switzerland
Hager Controls hereby declares that the Operation
instructions 8536 52 00 device complies with the essential
requirements and other relevant provisions of Directive
2014/53/EU.
The CE declaration is available on the:
www.hagergroup.com
6LE003100C

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 8536 52 00 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Berker 8536 52 00

  • Page 1 Switzerland Installation Angle fixing support 8590 02 00 Hager Controls hereby declares that the Operation instructions 8536 52 00 device complies with the essential requirements and other relevant provisions of Directive 2014/53/EU. The CE declaration is available on the: www.hagergroup.com...
  • Page 2 Range : 100 m on open field Sensitivity : min. 20%, max. 100% Fixing accessories : corner support Berker GmbH & Co. KG - Zum Gunterstal - 66440 Blieskastel/Germany - Tel.: +49 6842 945 0 - Fax: +49 6842 945 4625 - E-Mail: info@berker.de - www.berker.com...

Table of Contents