T7000e
Parameter
Parameter Name
Item
Dry contact input function
P2
selection
Temperature display on
P3
the LCD screen
Conversion between
P4
Celsius and Fahrenheit
P5
Product model definition
P6
Application selection
FAN-8941(1123)
Parameter Setting
Range
(Default Value)
00: Key card function (open)
01: Key card function (closed)
02: External sensor
03: Dew point risk warning (open)
00
04: Dew point risk warning (closed)
05: The open circuit indicates that the room is occupied, while
the short circuit indicates that the room is unoccupied, and the
fans and valves are shut off.
00: The room temperature is displayed when it is in the normal state.
00
01: The set temperature is displayed when it is in the normal state.
00
00: Celsius (℃ ); 01: Fahrenheit (° F)
00: NG1; 01: NG2; 02: NG3: 03: NG4; 04: NG5
/
Users cannot modify them, and only product models are
displayed.
T7300-TF60-9KS0:
00: Support 2-pipe on-off 2/3-wire valves, 3-speed fans and
the TiO2/ESP function
01: Support 4-pipe on-off 2/3-wire valves and 3-speed fans
T7700-TF60-9KS0:
00: Support 2-pipe on-off 2/3-wire valves, 3-speed fans,
Modbus RTU communication and the TiO
01: Support 4-pipe on-off 2/3-wire valves, 3-speed fans and
Modbus RTU communication
T7300-TF60-9MS0:
00: Support 2-pipe on-off 2/3-wire valves, ECM fans and the
TiO2/ESP function
01: Support 2-pipe proportional control valves and 3-speed fans
02: Support 2-pipe proportional control valves, ECM fans and
the TiO2/ESP function
03: Support 4-pipe on-off 3-wire valves and ECM fans
04: Support 4-pipe on-off 2-wire valves, ECM fans and the
TiO
/ESP function
2
05: Support 4-pipe proportional control valves and 3-speed fans
T7700-TF60-9MS0:
00
00: Support 2-pipe on-off 2/3-wire valves, ECM fans, Modbus
RTU communication and the TiO
01: Support 2-tube proportional control valves, 3-speed fans
and Modbus RTU communication
02: Support 2-pipe proportional control valves, ECM fans,
Modbus RTU communication and the TiO
03: Support 4-pipe on-off 3-wire valves, ECM fans and Modbus
RTU communication
04: Support 4-pipe on-off 2-wire valves, ECM fans, Modbus
RTU communication and the TiO
05: Support 4-pipe proportional control valves, 3-speed fans
and Modbus RTU communication
T7300-TF61-9MS0:
00: Support 2-pipe on-off 2/3-wire valves, ECM fans and the
TiO2/ESP function
01: Support 2-pipe proportional control valves and 3-speed fans
02: Support 2-pipe proportional control valves, ECM fans and
the TiO2/ESP function
03: Support 4-pipe on-off 3-wire valves and ECM fans
04: Support 4-pipe on-off 2-wire valves, ECM fans and the
TiO
/ESP function
2
05: Support 4-pipe proportional control valves and 3-speed fans
Functional Meaning
/ESP function
2
/ESP function
2
/ESP function
2
/ESP function
2
English

Applicable Model

All
All
All
All
All