Riello BS2F-GPL Installation, Use And Maintenance Instructions page 47

Forced draught gas burners
Table of Contents

Advertisement

Available languages

Available languages

3.
INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1
HEAT GENERATOR FIXING
Widen, if necessary, the insulating gasket holes (3, fig. 3).
Fix the flange (5) to the heat generator door (1) using four screws (4) and (if necessary) the nuts (2)
interposing the insulating gasket (3) but keep unloosing one of the two upper screws (4) (see fig. 2).
Put on the flange (5) the burner combustion head, tighten the flange with the screws (6) and lock the
loose screw (4).
N.B.: The burner can be fixed with the variable dimension (A) (see fig. 4). Anyway, make sure that the
combustion head crosses completely the heat generator door thickness.
Fig. 2
3.2
WORKING POSITION
The burner is designed to work
only in the positions 1, 2, 3, 5, 6
and 7.
The installation layout illustrated
in position 5 is only possible us-
ing the "MULTI-BLOC rotation
kit", to be ordered separately.
Any other position could compro-
mise the correct working of the
appliance. Installation 3 are for-
bidden for safety reasons.
20098824
6
3
5
4
20087421
1
5
2
1
TYPE
A
912 T2
114 - 100
913 T2
128 - 110
914 T2
167.5 - 145
2
6
7
GB
Fig. 3
D5012
A
Fig. 4
20087422
3
4
7
20087424

Advertisement

Chapters

Table of Contents
loading

Table of Contents