Riello BS2F-GPL Installation, Use And Maintenance Instructions page 43

Forced draught gas burners
Table of Contents

Advertisement

Available languages

Available languages

LPG KIT
There is a special kit available that, when mounted on the combustion head, enables burners designed to
run off natural gas to burn LPG instead. Refer to the instructions supplied with the "LPG kit" for installation.
The kit must be installed in conformity with laws and local regulations.
ALTERNATIVE COMBUSTION HEAD KIT
The kit can be used to avoid combustion instability that might be encountered in special applications.
The kit must be installed in conformity with laws and local regulations.
SEAL CONTROL KIT
There is a special kit available that can be used to check the seal of the gas train's valve.
This kit cannot be used for gas trains with valve model MULTIBLOC MBDLE 055.
The kit must be installed in conformity with laws and local regulations.
2.
TECHNICAL DATA
2.1
TECHNICAL DATA
Model
Burner delivery
(1)
Thermal power
(1)
Fuel
Main power supply
Fan motor
Capacitor
Ignition transformer
Absorbed electrical power
Model
Burner delivery
(1)
Thermal power
(1)
Fuel
Main power supply
Fan motor
Capacitor
Ignition transformer
Absorbed electrical power
Reference conditions: Temperature 20°C - Barometric pressure 1013 mbar – Altitude 0 m above sea level.
(1)
20098824
BS2F
35 − 91 kW
30.1 − 78.2 Mcal/h
Net heat value: 8 − 12 kWh/Nm
50 Hz
60 Hz
0.7 A absorbed
0,9 A absorbed
2835 g/min.
3245 rpm.
298 rad/s
341 rad/s
4 μF
Primary 230V / 0,2A - Secondary 8 kV / 12 mA
0.155 kW
0.20 kW
BS2F-GPL
35 − 91 kW
30.1 − 78,2 Mcal/h
Net heat value: 24 − 34 kWh/Nm
Single phase, 50/60Hz
50 Hz
60 Hz
0.7 A absorbed
0.9 A absorbed
2835 rpm.
3245 rpm.
298 rad/s
341 rad/s
4 μF
Primary 230V / 0,2A - Secondary 8 kV / 12 mA
0.155 kW
0.20 kW
BS3F
65 − 200 kW
55.9 − 172 Mcal/h
3
= 7000 − 10.340 kcal/Nm
Pressure: min. 20 mbar – max. 65 mbar
~
Single phase, 50/60Hz
220/230V ± 10%
50 Hz
60 Hz
1.6 A absorbed
2.2 A absorbed
2790 rpm.
3070 rpm.
293 rad/s
322 rad/s
6.3 μF
0.355 kW
0.485 kW
BS3F-GPL
65 − 200 kW
55.9 − 172 Mcal/h
3
= 21.000 − 29.000 kcal/Nm
Pressure: min. 20 mbar – max. 100 mbar
~
220/230V ± 10%
50 Hz
60 Hz
1.6 A absorbed
2.2 A absorbed
2790 rpm.
3070 rpm.
293 rad/s
322 rad/s
6.3 μF
0.355 kW
0.485 kW
3
GB
BS4F
110 − 250 kW
94.6 − 215 Mcal/h
3
50 Hz
60 Hz
1.9 A absorbed
2.7 A absorbed
2740 rpm.
2845 rpm.
288 rad/s
299 rad/s
8 μF
0.42 kW
0.60 kW
BS4F-GPL
110 − 250 kW
94.6 − 215 Mcal/h
3
50 Hz
60 Hz
1.9 A absorbed
2.7 A absorbed
2740 rpm.
2845 rpm.
288 rad/s
299 rad/s
8 μF
0.42 kW
0.60 kW

Advertisement

Chapters

Table of Contents
loading

Table of Contents