Chengdu Ebyte Electronic Technology Co., Ltd.
turned off), it will be counted once.
Falling edge: When the falling edge is collected (counting when it is turned on, and not counting when it is
released), count once.
Level: Two edges are collected and counted once respectively.
Clearing method:
Automatic: The device will automatically clear the DI count value register (0x 09DF ~ 0x 09E6 ) every time it
is read.
Manual: Manual mode needs to write 1 to the clear signal register (0x 0AA7 ~ 0x 0AAE ), and each holding
register controls one clear signal respectively.
4.2.2 level output
Output according to the level set by the user, the switch characteristic of the level mode is similar to the
function of a self-locking switch.
4.2.3 Pulse output
After the switch output DO is turned on, the switch output DO is automatically turned off after maintaining the
set pulse width time (in ms). The pulse width setting range is 50~65535ms (the default is 50 ms ).
4.2.4 follow mode
According to the following source configured by the user (when the device has AI acquisition or DI detection
function, both DI or AI can be used as the following source, otherwise this function is useless) to change the relay
state, multiple outputs can follow the same follow source output, simply put DI detects the input, and automatically
outputs the relay that takes it as the following source (for example: DI is 1, DO is closed ). When the follow mode
is turned on, the follow source should be configured at the same time, otherwise it will follow the first input by
default.
4.2.5 reverse follow mode
According to the following source configured by the user (when the device has AI acquisition or DI detection
function, both DI or AI can be used as the following source, otherwise this function is useless) to change the relay
state, multiple outputs can follow the same follow source output, simply put DI detects the input, and automatically
outputs the relay as the following source (for example: DI is 1 , DO is disconnected ). When the follow mode is
turned on, the follow source should be configured at the same time, otherwise it will follow the first input by
default.
4.2.6 trigger flip mode
According to the following source configured by the user (when the device has AI acquisition or DI detection
Copyright © 2012–2023 , Chengdu Ebyte Electronic Technology Co., Ltd.
17
ME31- XAAX0440 _User Manual