Programming the controller:
EKA 183A is used to copy settings to an ERC21X controller.
It can also be used to copy settings from one ERC controller to another ERC controller of the same type, eg. the same
software version.
Programming steps:
EKA 183A is inserted into the controller.
The controller is connected to the electricity mains.
Steps
1- flashes
(checking)
2 - light up constant
(await press)
3 - to write to the
controller or
to write to the
programming key
4 - light up constant
(transfer finished)
Note: refer to the specific documentation (DKRCC.PD.R1.06.02) for further details
Data Transfer:
Two methods (Mode A or Mode B) can be selected for transferring data. Modes may vary based on product and
connected device as in below table.
The default mode is set as "Mode B", which can be used for ERC 21X series only.Refer to specific documentation
(DKRCC.PD.R1.06.02) for step by step process to change the Mode for ERC 10X and ERC 11X Series.
Product Type
ERC 10X Series
ERC 11X Series
ERC 21X Series
2 |DKRCC.EI.RL0.I2.02 / 520H10102
Illustration
YELLOW
YELLOW
~ 1 sec
GREEN
~ 4 sec
CONSTANT
GREEN
Plugged in Doking Station
Installation guide | EKA 183A
Observations and actions
The LED will flash YELLOW when the programming is
inserted into the controller. Here it is checked whether the
data can be transferred
Shortly afterwards, the LED constant light up YELLOW and
the data transfer can start
- Pressing the button on the top of EKA (1 sec) will transfer
data from the programming key to the controller
(GREEN LED flashes)
- Pressing the button on the top of EKA (4 sec) will transfer
data from the controller to the programming key
(RED LED flashes)
RED
The transfer has finished when the LED light up constant
green
Flashing red-green-red-green-red-green....... = fault.
If there is a fault indication, please check code no.,
SW version and Error code.
Refer to Technical brochure (DKRCC.PD.R1.06.02) for
more details
Mode Setting for Programming Key
Mode A
Mode A
Not applicable
Connected to ERC product directly
Not applicable
Not applicable
Mode B
© Danfoss | DCS (az) | 2015.05