Setting The Heat Curve - Line C - Danfoss ECL Comfort 301 User Manual

Hide thumbs Also See for ECL Comfort 301:
Table of Contents

Advertisement

20a
Setting the heat curve -
line C
1
1
2
ON
ON
C
1
8
Slope
Circuit
Setting range
I
0.2 ... 3.4
The symbol for the slope of the heat curve
will blink. Adjust the slope of the heat curve, if
required.
o
C
1.8
2.2
2.6
3.0
110
1.4
100
90
1.0
80
70
0.6
60
50
40
0.2
30
20
10
-30
-20
-10
How to determine another heat curve, if necessary:
Choose the calculated flow temperature for your system and
the determined min. outdoor temperature for your area.
Pick the heat curve closest to the crossing point of these two
values.
The setting of the desired room temperature has an influence
on the calculated flow temperature (heat curve), no matter if a
room temperature sensor is connected or not.
Whether it is reasonable to change the slope or parallel
displacement will depend on the individual heat requirement.
Small increases or reductions in the heating temperature can be
implemented by means of the parallel displacement.
The grey
side of the
ECL Card
2
3
ON
Slope
0
Displacement
Factory setting
0.8
3.4
0
10
20
Parallel displacement
Circuit
I
If you want to adjust the parallel displacement of
the heat curve, push the shift button. The symbol
for the parallel displacement will blink.
Make your adjustments.
o
C
Setting range
Factory setting
-9 ... 9 K
The grey
side of the
ECL Card
20b
0 K

Advertisement