Consider the distribution of air from the indoor unit to the home and select a suitable position in
order to achieve a uniform air temperature in the place of installation.
•
Make sure that there are no sources of heat and/or steam nearby.
•
Maintain good air circulation.
•
Consider adopting measures to reduce noise.
•
Do not install the unit near doors and/or windows.
•
Make sure that the indoor unit is installed at a distance of not less than 15 cm from the roof and
side walls so as to ensure the air intake from the environment.
•
Install the indoor unit at least 2.3 meters from the floor.
OUTDOOR UNIT
•
lf you decide to protect the outdoor unit from rain and
direct sunlight with a special canopy, be careful not to
hinder heat radiation by the compressor.
•
Do not grow plants or raise animals in the vicinity of
the compressor because the heat could affect normal
growth.
•
Make sure there is a suitable distance from ceilings,
walls, furniture and other obstacles.
•
Secure the unit away from heat sources and/or
flammable gases.
•
The installation base and support frame must be
adequate and
secure.
installed on a flat surface.
LENGTH OF REFRIGERANT CONNECTIONS
Before installing the equipment, consider the maximum length of the refrigerant connections:
Minimum distance Outdoor/indoor units (m)
Maximum distance Outdoor/indoor units (m)
Maximum height difference (m)
Max distance with precharge (m)
Additional charge (g/m)
The machine must normally be
> than 30 cm
> than 200 cm
LSGT25-S
LSGT35-S
5
5
20
20
10
10
7
7
15
15
10
> than 60 cm
> than 10 cm
LSGT50-S
LSGT70-S
5
5
25
25
15
15
7
7
25
30