Manufacturer-Specific Gsd; Profile Gsd; Compatibility With Earlier Model; Automatic Identification - Endress+Hauser Proline Promass I 300 PROFIBUS DP Operating Instructions Manual

Coriolis flowmeter
Table of Contents

Advertisement

Proline Promass I 300 PROFIBUS DP
Endress+Hauser
9.2.1

Manufacturer-specific GSD

This GSD guarantees the unrestricted functionality of the measuring device. Device-specific
process parameters and functions are therefore available.
Manufacturer-specific GSD
PROFIBUS DP
The fact that the manufacturer-specific GSD should be used is specified in the Ident
number selector parameter by selecting the Manufacturer option.
Where to acquire the manufacturer-specific GSD:
www.endress.com
→ Downloads area
9.2.2

Profile GSD

Differs in terms of the number of Analog Input blocks (AI) and the measured values. If a
system is configured with a Profile GSD, it is possible to exchange devices made by
different manufacturers. However, it is essential to ensure that the order of the cyclic
process values is correct.
ID number
Supported blocks
0x9740
• 1 Analog Input
• 1 Totalizer
0x9741
• 2 Analog Input
• 1 Totalizer
0x9742
• 3 Analog Input
• 1 Totalizer
The Profile GSD that is to be used is specified in the Ident number selector parameter by
selecting the Profile 0x9740 option, Profile 0x9741 option or Profile 0x9742 option.
9.3

Compatibility with earlier model

If the device is replaced, the Promass 300 measuring device supports the compatibility of
the cyclic data with previous models. It is not necessary to adjust the engineering
parameters of the PROFIBUS network with the Promass 300 GSD file.
Previous model:
Promass 83 PROFIBUS DP
– ID No.: 1529 (hex)
– Extended GSD file: EH3x1529.gsd
– Standard GSD file: EH3_1529.gsd
9.3.1
Automatic identification (factory setting)
The Promass 300 PROFIBUS DP automatically recognizes the measuring device configured
in the automation system (Promass 83 PROFIBUS DP) and makes the same input and
output data and measured value status information available for cyclic data exchange.
Automatic identification is set in the Ident number selector parameter using the
Automatic mode option (factory setting).
ID number
File name
0x156F
EH3x156F.gsd
Supported channels
• Channel Analog Input: volume flow
• Channel totalizer: volume flow
• Channel Analog Input 1: volume flow
• Channel Analog Input 2: mass flow
• Channel totalizer: volume flow
• Channel Analog Input 1: volume flow
• Channel Analog Input 2: mass flow
• Channel Analog Input 3: corrected volume
flow
• Channel totalizer: volume flow
System integration