Download Print this page

Siemens GCA 1 Series Mounting Instructions page 10

Rotary-type spring return actuator
Hide thumbs Also See for GCA 1 Series:

Advertisement

en
Wire
Connection
designations
Actuators
AC 24 V
DC 24...48 V
Actuators
AC 230 V
Auxiliary switch
Feedback
potentiometer
fr
Câbles de rac-
Désignation
cordement
des câbles
servo-moteurs
AC 24 V
DC 24...48 V
servo-moteurs
AC 230 V
commutateurs
auxiliaires
potentiomètre
de retour
10/12
2023-02-09
Cable
Code
No.
Color
G
1
red
G0
2
black
Y1
6
purple
Y2
7
orange
Y
8
grey
U
9
pink
L
3
brown
N
4
blue
Q11
S1
grey/red
Q12
S2
grey/blue
Q14
S3
grey/pink
Q21
S4
black/red
Q22
S5
black/blue
Q24
S6
black/pink
a
P1
white/red
b
P2
white/blue
c
P3
white/pink
Câble
Code
No.
Couleurs
G
1
rouge
G0
2
noir
Y1
6
violet
Y2
7
orange
Y
8
gris
U
9
rose
L
3
brun
N
4
bleu
Q11
S1
gris/rouge
Q12
S2
gris/bleu
Q14
S3
gris/rose
Q21
S4
noir/rouge
Q22
S5
noir/bleu
Q24
S6
noir/rose
a
P1
blanc/rouge
b
P2
blanc/bleu
c
P3
blanc/rose
M4613
431926150-AL
Meaning
Abbreviatio
n
RD
System potential AC 24 V / DC 24...48 V
BK
System neutral
VT
Pos. signal AC 0 V, AC 24 V / DC 24...48 V, "open"
OG
Pos. signal AC 0 V, AC 24 V / DC 24...48 V,"close"
GY
Pos. signal DC 0...10 V, 0...35 V
PK
Position indication DC 0...10 V
BN
Line AC 230 V
BU
Neutral
GYRD
Switch A input
GYBU
Switch A normally-closed contact
GYPK
Switch A normally-open contact
BKRD
Switch B input
BKBU
Switch B normally-closed contact
BKPK
Switch B normally-open contact
WHRD
Potentiometer 0...100 % (P1-P2)
WHBU
Potentiometer pick-off
WHPK
Potentiometer 100...0 % (P3-P2)
Signification
Abbreviatio
n
RD
potentiel du système AC 24 V / DC 24...48 V
BK
zéro du système
VT
signal de commande AC 0 V, AC 24 V / DC24...48 V, "ou-
vrir"
OG
signal de commande AC 0 V, AC 24 V / DC24...48 V, "fer-
mer"
GY
signal de commande DC 0...10 V, 0...35 V
PK
signal de position DC 0...10 V
BN
Phase AC 230 V
BU
neutre
GYRD
commutateur A entrée
GYBU
commutateur A contact de repos
GYPK
commutateur A contact de travail
BKRD
commutateur B entrée
BKBU
commutateur B contact de repos
BKPK
commutateur B contact de travail
WHRD
potentiomètre 0...100 % (P1-P2)
WHBU
potentiomètre curseur
WHPK
potentiomètre 100...0 % (P3-P2)
Smart Infrastructure