Parameter:
E08
Description:
Indoor temp. calibration.
Available settings:
-9.0~+9.0
Default setting:
0.0
Parameter:
E10
Description:
Externaltemp. calibration.
Available settings:
-9.0~+9.0
Default setting:
0.0
Parameter:
E11
Description:
Function option of external temp. sensor.
0: External temperature sensor work as high temperature protection detection
1: External temperature sensor work as main control temperature
Available settings:
0~1
Default setting:
0
Parameter:
E12
Description:
Anti-Freeze protection switch.
ON: Turn on
OFF: Turn off
Default protection temperature range: (5.0°C - 8.0°C)
Anti-Freeze feature is available only when heating mode,
turn on when temperature decrease to 5.0°C, turn off when temperature increase to 8.0°C
Available settings:
ON / OFF
Default setting:
OFF
Parameter:
E13
Description:
Fan mode option when indoor
temperature reaches to setting temp.
ON: fan keep low speed
OFF: fan turned off
Available settings:
ON/OFF
Default setting:
OFF
Parameter:
E14
Description:
Fan working mode.
0: Fan works both for cooling and heating mode
1: Fan works only in cooling mode
2: Fan works only in heating mode
3: Fan not work neither in cooling nor heating mode
Available settings:
0~3
Default setting:
0