Nice Fan4-Control Instructions And Warnings For Installation And Use page 13

Z-wave fan coil thermostat for 4-pipe installations
Table of Contents

Advertisement

11
Z-WAVE PARAMETER SETTING
Table A7 Z-Wave parameter setting
Parameter:
1. Paremeter Menu No. E20 Temp. Unit
Description:
0: Celsius
1: Fahrenheit
Available settings:
0-1
Default setting:
1
Parameter:
2. Automatic Temperature Value Reporting (Celsius)
Description:
Unit 0.1
0: OFF:
3-255: n *0.1,automatically report to gateway when temperature variation greater than this value.
Available settings:
0,3-255
Default setting:
5
Parameter:
2. Automatic Temperature Value Reporting (Celsius)
Description:
Unit 0.1 F:
0: OFF:
3-255: n *0.1F,automatically report to gateway when temperature variation greater than this value.
Available settings:
0,3-255
Default setting:
10
Parameter:
3. Automatic Humidity Value Reporting
Description:
0: OFF
1-99: Automatically report to gateway when humidity variation greater than this value.
Available settings:
0-99
Default setting:
6
Parameter:
12. Paremeter Menu No. E02: Power Failure Memory
Description:
When power on again:
0:device will be in shutdown state ("OFF");
1: device will be in working interface;
2: device will stay the last status before power failure.
Available settings:
0-2
Default setting:
1
Parameter:
13. Paremeter Menu No. E03: Backlight Brightness
Description:
1: dim, dim without key touch
2: Low brightness
3: Medium brightness
4: High brightness
5: Always on
Available settings:
1-5
Default setting:
2
Parameter:
14. Paremeter Menu No. E04: Beep
Description:
1: OFF2 Low Beep
3: Medium Beep
4: High Beep
5: Standard Beep
Available settings:
Default setting:
0
Parameter size:
1 [byte]
Parameter size:
2 [byte]
Parameter size:
2 [byte]
Parameter size:
1 [byte]
Parameter size:
1 [byte]
Parameter size:
1 [byte]
Parameter size:
1 [byte]