GENERAL DESCRIPTION
The Star Galaxy SGQR and SG, 8.0 K-Factor, QR-EC
and EC Horizontal Sidewall and Recessed Horizontal
Sidewall Sprinklers are extended coverage, decorative
glass bulb type spray sprinklers designed for use in hy-
draulically calculated sprinkler systems in light, commer-
cial occupancies such as churches, restaurant seasting
areas, hotels, educational facilities, offices, etc. With cov-
erage areas up to 16 feet (4,9 m) wide by 24 feet (7,3 m)
long, they are designed for installation along a wall or the
side of a beam and just beneath a smooth and level ceil-
ing. Horizontal sidewall sprinklers are commonly used in-
stead of pendent or upright sprinklers because of aesthet-
ics or building construction considerations, where piping
across the ceiling is not desirable.
The SGQR (3 mm bulb type) is for quick response ex-
tended coverage applications, and in some cases stand-
ard response extended coverage applications. The SG (5
mm bulb type) is only for standard response extended
coverage applications. Refer to Tables A-1 and A-2 for de-
tails.
The recessed version of the Star Galaxy SGQR and SG,
intended for use in areas with concealed piping and a fin-
ished wall, uses a two-piece #2086 or #2088 Recessed
Escutcheon. The #2086 provides 1/4 inch (6,4 mm) of re-
cessed adjustment or up to 1/2 inch (12,7 mm) of total ad-
justment from the flush sidewall position, and the #2088
provides 1/2 inch (12,7 mm) of recessed adjustment or
up to 3/4 inch (19,1 mm) of total adjustment from the
flush sidewall position. The adjustment provided by the
Recessed Escutcheon reduces the accuracy to which the
fixed pipe nipples to the sprinklers must be cut.
WARNINGS
The Star Galaxy SGQR and SG Sprinklers described
herein must be installed and maintained in compliance
with this document, as well as with the applicable stand-
ards of the National Fire Protection Association, in addi-
tion to the standards of any other authorities having juris-
diction. Failure to do so may impair the integrity of these
devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
TYCO FIRE PRODUCTS
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500
SIN S2983
SGQR (3 mm bulb)
SIN S2813
SG (5 mm bulb)
Shown With
#2088 Recessed
OPERATION
The glass bulb contains a fluid which expands when ex-
posed to heat. When the rated temperature is reached,
the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM Approved.
(Refer to Table A-1 and A-2. The approvals apply only to
the service conditions indicated in the Design Criteria sec-
tion. Refer to Table B for Recessed Escutcheon approv-
als.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
3/4 inch NPT
Discharge Coefficient
1/2
K = 8.0 GPM/psi
(115,2 LPM/bar
Temperature Ratings
SGQR: 135°F/57°C, 155°F/68°C, or 175°F/79°C
SG: 135°F/57°C or 155°F/68°C
Finishes
Sprinkler: White Polyester, Black Polyester,
Chrome Plated, Natural Brass
Recessed Escutcheon: White Coated, Black Coated,
Chrome Plated, Bright Brass Plated
(Other colors are available on request.)
Physical Characteristics (Ref. Figure 1)
The Star Galaxy utilizes a dezincification resistant (DZR)
bronze frame, and either a 3 mm diameter (SGQR) or 5
mm diameter (SG) glass bulb. The two-piece button as-
sembly is brass and copper. The gasketed spring plate
consists of a beryllium nickel disc spring that is sealed on
both its inside and outside edges with a Teflon
The compression screw is bronze, and the deflector is
brass.
Escutcheon
1/2
)
V
gasket.
1-2.3.41