Download Print this page

Tyco Fire Product Star Galaxy SG Instruction Manual

Std. response - std. coverage upright, pendent, and recessed pendent sprinklers

Advertisement

Quick Links

Std. Response - Std. Coverage
Upright, Pendent, and
Recessed Pendent Sprinklers
Star Galaxy™ SG, K=8.0, 3/4" NPT
GENERAL DESCRIPTION
The Star Galaxy SG, 8.0 K-Factor, Upright, Pendent, and
Recessed Pendent Sprinklers are standard response -
standard coverage, decorative glass bulb type spray
sprinklers designed for use in light, ordinary, or extra haz-
ard, commercial occupancies such as banks, hotels,
shopping malls, factories, refineries, chemical plants, etc.
The recessed version of the Star Galaxy SG, intended for
use in areas with a finished ceiling, uses a two-piece
#2086 Recessed Escutcheon. The #2086 provides 1/2
inch (12,7 mm) of recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the flush pendent posi-
tion. The adjustment provided by the Recessed Escutch-
eon reduces the accuracy to which the fixed pipe drops to
the sprinklers must be cut.
Wax and lead coatings are utilized to extend the life of
copper alloy sprinklers beyond that which would other-
wise be obtained when exposed to corrosive atmos-
pheres. Although wax and lead coated sprinklers have
passed the standard corrosion tests of the applicable ap-
proval agencies, the testing is not representative of all
possible corrosive atmospheres. Consequently, it is rec-
ommended that the end user be consulted with respect to
the suitability of these corrosion resistant coatings for any
given corrosive environment. The effects of ambient tem-
perature, concentration of chemicals, and gas/chemical
velocity, should be considered, as a minimum, along with
the corrosive nature of the chemical to which the sprin-
klers will be exposed.
An intermediate level version of the Star Galaxy SG Pen-
dent Sprinkler can be obtained by utilizing the Star Gal-
axy SG Pendent Sprinkler (SIN S2811) in combination
with the Model S11 Shield described in Product Data
Sheet 1-4.2.40.
WARNINGS
The Star Galaxy SG Sprinklers described herein must be
installed and maintained in compliance with this docu-
ment, as well as with the applicable standards of the Na-
tional Fire Protection Association, in addition to the stand-
ards of any other authorities having jurisdiction. Failure to
do so may impair the integrity of these devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
TYCO FIRE PRODUCTS
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500
SIN S2810
SIN S2811
Upright
Pendent
OPERATION
The glass bulb contains a fluid which expands when ex-
posed to heat. When the rated temperature is reached,
the fluid expands sufficiently to shatter the glass bulb,
which then allows the sprinkler to activate and flow water.
TECHNICAL DATA
Approvals
UL and ULC Listed. FM, LPC, NYC Approved.
(Refer to Table A. The approvals apply only to the service
conditions indicated in the Design Criteria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Pipe Thread Connection
1/2 inch NPT
Discharge Coefficient
1/2
K = 8.0 GPM/psi
(115,2 LPM/bar
Temperature Ratings
135°F/57°C, 155°F/68°C, 175°F/79°C,
200°F/93°C, 286°F/141°C, or 360°F/182°C
(Refer to Table A)
Finishes
Sprinkler: White Polyester, Black Polyester,
Chrome Plated, Natural Brass, Wax Coated, Lead Coated,
Wax over Lead Coated (Refer to Table A)
Recessed Escutcheon: White Coated, Black Coated,
Chrome Plated, Bright Brass Plated
(Other colors are available on request.)
Physical Characteristics (Ref. Figure 1)
The Star Galaxy SG utilizes a dezincification resistant
(DZR) bronze frame, and a 5 mm diameter glass bulb.
The two-piece button assembly is brass and copper. The
gasketed spring plate consists of a beryllium nickel disc
spring that is sealed on both its inside and outside edges
V
with a Teflon
gasket. The compression screw is bronze,
and the deflector is brass.
DESIGN CRITERIA
The 8.0 K-Factor, Star Galaxy SG Upright, Pendent, and
Recessed Pendent Sprinklers are intended for fire protec-
tion systems designed in accordance with the standard in-
stallation rules recognized by the applicable Listing or Ap-
proval agency (e.g., UL Listing is based on NFPA 13
requirements). Only the #2086 Recessed Escutcheon de-
scribed herein is to be used for recessed installations.
Shown With
#2086 Recessed
Escutcheon
1/2
)
1-1.2.50
3-01

Advertisement

loading
Need help?

Need help?

Do you have a question about the Star Galaxy SG and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco Fire Product Star Galaxy SG

  • Page 1 UL and ULC Listed. FM, LPC, NYC Approved. (Refer to Table A. The approvals apply only to the service The recessed version of the Star Galaxy SG, intended for conditions indicated in the Design Criteria section.) use in areas with a finished ceiling, uses a two-piece #2086 Recessed Escutcheon.
  • Page 2 The The Star Galaxy SG Pendent and Upright Sprinklers jaws of the wrench should be opened sufficiently wide to must be installed in accordance with the following instruc- pass over the wrenching flanges without damaging the tions.
  • Page 3 #2086 Closure over proximately one-half inch away from the area requiring re- the Star Galaxy SG Sprinkler and push the Closure over touching. The wax will melt and run down onto the sprin- the Mounting Plate until its flange comes in contact with kler.
  • Page 4 This warranty will expire ten (10) years from date of shipment by Tyco Fire Products. No warranty The Star Galaxy SG Sprinklers must be maintained and is given for products or components manufactured by serviced in accordance with the following instructions:...