Std. Response - Std. Coverage
Star Galaxy™ SG Easy Guard
K=8.0 Sprinklers With Guards
& Intermediate Level Sprinklers
with Guards
Quick Response - Std. Coverage
Star Galaxy™ SGQR Easy Guard
K=8.0 Sprinklers With Guards
& Intermediate Level Sprinklers
with Guards

GENERAL DESCRIPTION

The Star Galaxy Easy Guard, 8.0 K-Factor (17/32 ori-
fice), Sprinklers are standard coverage, glass bulb type
spray sprinklers. The SG (5 mm bulb type) Sprinklers are
"standard response", and the SGQR (3 mm bulb type)
Sprinkler are "quick response". The Easy Guard Sprin-
klers provides a unique factory assembled guard or guard
& shield, and its double groove frame design allows instal-
lation of the sprinkler without having to first remove the
guard or guard & shield, saving time and labor cost of
field installation.
Sprinklers with guards may be located in areas that make
them susceptible to being struck, so as to help prevent
damage to the sprinklers.
Intermediate Level Sprinklers (i.e, sprinklers with shields)
are primarily designed for use in rack storage sprinkler
systems, where their thermally sensitive elements must
be shielded from the water spay of higher elevation sprin-
klers which could operate earlier during a fire. Intermedi-
ate Level Sprinklers are also used in applications such as
beneath open gridded catwalks.
WARNINGS
The Star Galaxy SG Easy Guard Sprinklers described
herein must be installed and maintained in compliance
with this document, as well as with the applicable stand-
ards of the National Fire Protection Association, in addi-
tion to the standards of any other authorities having juris-
diction. Failure to do so may impair the integrity of these
devices.
The owner is responsible for maintaining their fire protec-
tion system and devices in proper operating condition.
The installing contractor or sprinkler manufacturer should
be contacted relative to any questions.
TYCO FIRE PRODUCTS
Customer Service/Sales: Tel: (800) 558-5236 • Fax: (414) 570-5010
Technical Services: Tel: (800) 381-9312 • Fax: (800) 791-5500
2-7/8"
(73.0 mm)
3-5/16"
(84.1 mm)
3/4" NPT
SIN S3410 SR Upright With Guard
SIN S3479 QR Upright With Guard
2-7/8"
(73.0 mm)
3/4"
NPT
3-5/16"
(84.1 mm)
SIN S3411 SR Pendent With Guard
SIN S3480 QR Pendent With Guard
4" DIA.
(101.6 mm)
3-3/8"
(85.7 mm)
3/4" NPT
SIN S3510 SR Upright With Guard and Shield
SIN S3579 QR Upright With Guard and Shield
3" DIA.
(76.2 mm)
3/4"
NPT
3-5/16"
(84.1 mm)
SIN S3511 SR Pendent With Guard and Shield
SIN S3580 QR Pendent With Guard and Shield
2-7/16"
(61.9 mm)
2-1/2"
(63.5 mm)
2-7/16"
(61.9 mm)
2-1/2"
(63.5 mm)
1-4.2.12
3-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Star Galaxy SG and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco Fire Product Star Galaxy SG

  • Page 1 3" DIA. ate Level Sprinklers are also used in applications such as (76.2 mm) beneath open gridded catwalks. WARNINGS The Star Galaxy SG Easy Guard Sprinklers described 3/4" 2-1/2" herein must be installed and maintained in compliance (63.5 mm) with this document, as well as with the applicable stand- 3-5/16"...
  • Page 2 STAR SPRINKLER 1-4.2.12 Page 2 OPERATION The glass bulb contains a fluid which expands when ex- posed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, which then allows the sprinkler to activate and flow water. WRENCH TECHNICAL DATA RECESS...
  • Page 3 STAR SPRINKLER Page 3 1-4.2.12 CARE AND MAINTENANCE LIMITED WARRANTY The Star Galaxy Easy Guard Sprinklers must be main- Products manufactured by Tyco Fire Products are war- tained and serviced in accordance with the following in- ranted solely to the original Buyer for ten (10) years structions: against defects in material and workmanship when paid for and properly installed and maintained under normal...
  • Page 4 1-4.2.12 STAR SPRINKLER Page 4 ORDERING PROCEDURE Please Specify: Standard Response 8.0 K-Factor, SG Easy Guard, Standard Response Upright Sprinkler with Guard (#3410) 8.0 K-Factor, SG Easy Guard, Standard Response Pendent Sprinkler with Guard (#3411) 8.0 K-Factor, SG Easy Guard, Standard Response Upright Sprinkler with Guard and Shield (#3510) 8.0 K-Factor, SG Easy Guard, Standard Response Pendent Sprinkler with Guard and Shield (#3511)

Table of Contents