Gas Heat Minimum Supply Air - York ZH078 Installation Manual

Hide thumbs Also See for ZH078:
Table of Contents

Advertisement

Table 13: Gas Heat Minimum Supply Air
Size
Model
(Tons)
078
ZH
(6.5)
090
ZH
(7.5)
102
ZH
(8.5)
120
ZH
(10)
150
ZH
(12.5)
Gas Connection
The gas supply line can be routed within the space and roof curb,
exiting through the unit's basepan. Refer to Figures 8 and 9 for
the gas piping inlet location. Typical supply piping arrangements
are shown in Figures 25 and 26. All pipe nipples, fittings, and the
gas cock are field supplied or may be purchased in Ducted
Systems accessory kit #1GP0405.
Gas piping recommendations:
1.
A drip leg and a ground joint union must be installed in the
gas piping.
2.
Where required by local codes, a manual shut-off valve
must be installed outside of the unit.
3.
Use wrought iron or steel pipe for all gas lines. Pipe dope
should be applied sparingly to male threads only.
Natural gas may contain some propane. Propane is an
excellent solvent and will quickly dissolve white lead and
most standard commercial compounds. A special pipe
dope must be used when assembling wrought iron or
steel pipe. Shellac based compounds such as Gaskolac
or Stalastic, and compounds such as Rectorseal #5,
Clydes's or John Crane may be used.
4.
All piping should be cleaned of dirt and scale by
hammering on the outside of the pipe and blowing out
loose particles. Before initial start-up, be sure that all gas
lines external to the unit have been purged of air.
5.
The gas supply should be a separate line and installed in
accordance with all safety codes as prescribed under
"Limitations".
6.
A 1/8-inch NPT plugged tapping, accessible for test gage
connection, must be installed immediately upstream of the
gas supply connection to the unit.
7.
After the gas connections have been completed, open the
main shut-off valve admitting normal gas pressure to the
mains. Check all joints for leaks with soap solution or other
material suitable for the purpose. NEVER USE A FLAME.
Johnson Controls Ducted Systems
Heat Size
Min
N12
1950
N18
1950
N12
2250
N18
2250
N12
2550
N18
2550
N18
3000
N24
3000
N18
3750
N24
3750
Lp Units, Tanks And Piping
All gas heat units are shipped from the factory equipped for
natural gas use only. The unit may be converted in the field for
use with LP gas with accessory kit model number 1NP0442.
All LP gas equipment must conform to the safety standards of
the National Fire Protection Association.
Supply Air (CFM)
Cooling
Max
Min
3250
1950
3250
1950
3750
2250
3750
2250
4250
2550
4250
2550
5000
3000
5000
3000
6250
3750
6250
3750
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warning exactly could result
in serious injury, death or property damage.
Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically
for the detection of leaks to check all connections. A fire
or explosion may result causing property damage,
personal injury or loss of life.
The furnace and its individual shut-off valve must be
disconnected from the gas supply piping system during
any pressure testing at pressures in excess of 1/2 PSIG.
Pressures greater than 1/2 PSIG will cause gas valve
damage resulting in a hazardous condition. If it is
subjected to a pressure greater than 1/2 PSIG, the gas
valve must be replaced.
The furnace must be isolated from the gas supply piping
system by closing its individual manual shut-off valve
during any pressure testing of the gas supply piping
system at test pressures equal to or less than 1/2 PSIG.
Threaded joints should be coated with a sealing
compound that is resistant to the action of liquefied
petroleum gases. Do not use Teflon tape.
5167515-YIM-H-0518
Heating
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
33