York ZV-06 Installation Manual page 26

Table of Contents

Advertisement

5567611-BIM-B-1218
ZV-06 through -12 standard indoor blower - without powered convenience outlet (Continued)
Compressors (each)
Size
RLA
LRA
Volt
(tons)
C1
C2
C1
208 17.6 17.6 136 136
-12
230 17.6 17.6 136 136
(12.5)
460
8.5
8.5 66.1 66.1
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
26
OD fan
Supply
motors
blower
MCC
(each)
motor
C2
C1
C2
FLA
FLA
27
27
3.5
9.6
27
27
3.5
9.6
13
13
1.6
4.7
Pwr
Pwr
exh.
conv.
Electric heat option
motor
outlet
FLA
FLA
Model
kW
Stages
None
-
E18
13.5
5.5
E24
18
E36
25.5
E54
40.6
None
-
E18
18
5.5
E24
24
E36
34
E54
54
None
-
E18
18
2.2
E24
24
E36
34
E54
54
1
MCA
1
MCA
with pwr
(amps)
exhaust
Amps
(amps)
-
-
63.2
68.7
2
37.5
63.2
68.7
2
50
74.5
81.4
2
70.8
100.5
107.4
2
112.7
152.9
159.8
-
-
63.2
68.7
2
43.3
66.1
73
2
57.7
84.1
91
2
81.8
114.3
121.1
2
129.9
141.9
148.8
-
-
30.2
32.4
2
21.7
33
35.8
2
28.9
42
44.8
2
40.9
57
59.8
2
65
70.9
73.6
Johnson Controls Ducted Systems
2
Max fuse
/
2
Max fuse
/
3
breaker
3
breaker
size with
size
pwr exh.
(amps)
(amps)
80
80
80
80
80
90
110
110
175
175
80
80
80
80
90
100
125
125
175
175
35
40
35
40
45
45
60
60
80
80

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zv seriesZv-07Zv-08Zv-10Zv-12