York ZV-06 Installation Manual page 32

Table of Contents

Advertisement

5567611-BIM-B-1218
ZV-06 through -12 high static indoor blower - with powered convenience outlet (Continued)
Compressors (each)
Size
RLA
LRA
Volt
(tons)
C1
C2
C1
208 17.6 17.6 136 136
-12
230 17.6 17.6 136 136
(12.5)
460
8.5
8.5 66.1 66.1
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
32
OD fan
Supply
motors
blower
MCC
(each)
motor
C2
C1
C2
FLA
FLA
27
27
3.5
14
27
27
3.5
14
13
13
1.6
6.6
Pwr
Pwr
exh.
conv.
Electric heat option
motor
outlet
FLA
FLA
Model
kW
Stages Amps
None
-
E18
13.5
5.5
20
E24
18
E36
25.5
E54
40.6
None
-
E18
18
5.5
20
E24
24
E36
34
E54
54
None
-
E18
18
2.2
20
E24
24
E36
34
E54
54
1
MCA
1
MCA
with pwr
(amps)
exhaust
(amps)
-
-
77.6
83.1
2
37.5
77.6
83.8
2
50
92.5
99.4
2
70.8
118.5
125.4
2
112.7
170.9
177.8
-
-
77.6
83.1
2
43.3
84.1
91
2
57.7
102.1
109
2
81.8
132.3
139.1
2
129.9
159.9
166.8
-
-
37.1
39.3
2
21.7
41.6
44.4
2
28.9
50.6
53.4
2
40.9
65.6
68.4
2
65
79.5
82.3
Johnson Controls Ducted Systems
2
Max fuse
/
2
Max fuse
/
3
breaker
3
breaker
size with
size
pwr exh.
(amps)
(amps)
90
100
90
100
100
100
125
150
175
200
90
100
90
100
110
110
150
150
175
175
45
45
45
45
60
60
70
70
90
90