APPLICATION GUIDELINES
General Mounting
General Mounting
The ceiling must be strong and solid enough to protect the unit from vibration. All ceiling-cassette indoor units include a pattern to help deter-
mine the size necessary for the opening in the false ceiling (paper pattern dimensions match those for the ceiling opening dimensions), and
where the hanging bolts and refrigerant / drain piping are placed.
Figure 80: Ceiling Opening / Hanging Bolt Locations for One-Way Ceil-
ing Cassette Indoor Units.
54-17/32 (Ceiling Opening)
1-31/32
23-5/8
50-19/32 (Hanging Bolt)
9-27/32
TT Frame
41-59/64 (Ceiling Opening)
1-31/32
23-5/8
37-63/64 (Hanging Bolt)
33-55/64
9-27/32
TU Frame
Figure 82: Ceiling Opening / Hanging Bolt Locations for Four-Way Ceiling Cassette Indoor Units.
TQ / TR Frame
23-1/32 ~ 23-5/8 (Ceiling opening)
20-23/64 (Hanging Bolt)
12-9/16
18-5/32 (Hanging Bolt)
Panel size : 24-13/32 x 24-13/32
98 | GUIDELINES
1-31/32
46-29/64
1-31/32
Unit: Inch
22-7/16
©
Figure 81: Ceiling Opening / Hanging Bolt Locations for Two-Way Ceil-
ing Cassette Indoor Units.
40-11/16 Ceiling Opening
33-11/16 Hanging Bolt
TA Frame
34-29/64
(Ceiling Opening)
30-63/64
(HangingBbolt)
33-5/64
Unit Size
2-3/8
32-11/16
(Unit: Inch)
Unit: Inch