Download Print this page

LG multi V ARNU073TUD4 Engineering Manual page 9

Ceiling cassette indoor unit
Hide thumbs Also See for multi V ARNU073TUD4:

Advertisement

System Tag or ID:
Line #
1
Linear feet of 1/4" liquid line tubing
2
Linear feet of 3/8" liquid line tubing
3
Linear feet of 1/2" liquid line tubing
4
Linear feet of 5/8" liquid line tubing
5
Linear feet of 3/4" liquid line tubing
6
Linear feet of 7/8" liquid line tubing
7
Linear feet of 1" liquid line tubing
8
Standard + Art Cool Mirror
9
Standard + Art Cool Mirror
10
Standard
11
Art Cool Gallery
12
1-Way Cassette
13
1-Way Cassette
14
2-Way Cassette
15
4-Way 2' x 2' Cassette
16
4-Way 2' x 2' Cassette
17
4-Way 2' x 2' Cassette
18
4-Way 3' x 3' Cassette
19
Mid Static Ducted
20
High Static Ducted
21
High Static Ducted
22
High Static Ducted
23
High Static Ducted
24
Low Static Ducted, Low Static Ducted Bottom Return
25
Low Static Ducted, Low Static Ducted Bottom Return
26
Low Static Ducted, Low Static Ducted Bottom Return
27
Vertical / Horizontal Air Handling Unit
28
Vertical / Horizontal Air Handling Unit
29
Vertical / Horizontal Air Handling Unit
30
Floor Standing
31
Floor Standing
32
HRU: PRHR022A/023A, 032A/033A, 042A/043A
33
HRU: PRHR063A, 083A
34
Total Outdoor Unit Factory Refrigerant
35
Charge (Choose One)
36
Sum of Additional Refrigerant Charge Required (line 34) and Total ODU Factory Refrigerant Charge (from line 35A to 35F)
CF (Ref.) = Correction Factor for Refrigerant Charge.
1
REFRIGERANT CHARGE WORKSHEET
Multi V S System R410A Refrigerant Charge Calculator (lbs.)
Job Name: __________________________________________
Project Manager: ____________________________________
Description
2
2
2
2
2
2
2
35A
35B
35C
35D
35E
35F
For refrigerant charge purposes, consider only the liquid line; ignore the vapor line(s).
2
©
Chassis I.D.
Size
SJ, SK
5k to 15k
SJ, SK
18k to 24k
SV
30k to 36k
SF
9k to 12k
TU
7k to 12k
TT
18k to 24k
TS
18k to 24k
TR
5k to 7k
TR
9k to 12k
TQ
15k to 18k
TA
7k to 48k
M1
7k to 24k
M2
7k to 24k
M2
28k to 42k
M3
28k to 54k
B8
36k to 96k
L1
5k to 9k
L2
12k to 18k
L3
21k to 24k
NJ
12k to 30k
NJ
36k
NK
42k to 54k
CE (U)
7k to 15k
CF (U)
18k to 24k
ADDITIONAL Refrigerant Charge Required (Sum of lines 1 – 33)
ARUN024GSS4
ARUN038GSS4
ARUN048GSS4
ARUN053GSS4
ARUN060GSS4
ARUB060GSS4
Date: ______________
Quantity
CF (Ref.)
1
0.015
0.041
0.079
0.116
0.179
0.238
0.323
0.53
0.62
1.01
0.22
0.44
0.64
0.75
0.40
0.55
0.71
1.5
0.57
0.77
1.15
1.35
2.20
0.31
0.42
0.55
1.04
1.57
2.00
0.37
0.82
1.1
2.2
0
0
0
0
0
0
TOTAL SYSTEM CHARGE
INTRODUCTION | 9
Total (lbs.)

Advertisement

loading