Single Ups Installation - Orvaldi V10KRT User Manual

Online ups
Table of Contents

Advertisement

8. External battery connector
9. Line input terminal
10. Output terminal
11. Bypass input terminal
12. Input grounding terminal
13. Output grounding terminal
14. RS232 Port

2-3. Single UPS Installation

Installation and wiring must be carried out in accordance with the local electric laws and regulations by
trained professionals.
1)
Make sure that the mains wire and breakers of the building are rated for the capacity of the UPS to
prevent electric shock or risk of fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than
the UPS's maximum input current. The receptacle may be damaged and destroyed.
2) Switch off the mains switch in the building before installation.
3) Turn off all the connected devices before connecting to the UPS.
4) Prepare wires based on the following table:
Model
V10KRT 3/3
V10KRT 3/1
V15KRT 3/1
V15KRT 3/1
V20KRT 3/3
V20KRT 3/1
NOTE : The selections for color of wires should be followed by the local electrical laws and regulations.
5)
Remove the terminal block cover at the rear panel of UPS. Then connect the wires according to the
following terminal block diagrams: (Connect the grounding/earthing wire first when making other wire
connections. Remove the grounding/earthing wire last when connecting the UPS!)
NOTE: For dual input model with single input power system, connect input terminals to the AC power
source and connect input and bypass input together (shows dashed line in below wiring diagrams)
Input(Ph)
Bypass(Ph)
14
14
14
8
12
12
12
6
10
10
10
4
Wiring spec (AWG)
Output(Ph)
Neutral
14
10
8
8
12
10
6
6
10
6
4
4
6
Battery
Ground
8
8
8
8
8
6
8
6
4