4.6.1. DO Register List

Register
Register function
address
DO status
0x0000
State when DO is
0x0064
powered on
DO working
0x0578
mode
DO pulse width
0x05DC
DO Follow
Source
Copyright ©2012–2023, Chengdu Ebyte Electronic Technology Co.,Ltd
Register
type
Coil
Holding
register
Holding
register
Holding
register
DI:0x0000
Holding
AI:0x8000
register
Number Operate
Data Range/Remarks
Write to change the
current DO state, read
6
RW
to obtain the current
DO state
The default state of the
6
RW
coil after power on
0x0000 level no follow
mode
0x0001 Pulse no follow
mode
6
RW
0x0002 Follow mode
0x0003
Follow Mode
0x0004 Trigger Flip
Mode
6
RW
Range: 50-65535ms
Scope:
0x0000: Follow DI1
6
RW
0x0001: Follow DI2
0x8000: Follow AI1
0x8001: Follow AI2
ME31-XXAX0060_UserManual_EN
Related
function code
R:0x01
W: 0x0F、 0x05
R:0x01
W: 0x0F、 0x05
R:0x03
W: 0x06、 0x10
Reverse
R:0x03
W: 0x06、 0x10
R:0x03
W: 0x06、 0x10
20

Advertisement

Table of Contents
loading

Table of Contents