Modbus Rtu Protocol Data Frame Description; Modbus Parameter Configuration; Do Register List - Ebyte ME31-AAAX2240 User Manual

I/o networking module
Hide thumbs Also See for ME31-AAAX2240:
Table of Contents

Advertisement

Chengdu Ebyte Electronic Technology Co.,Ltd.
after each communication to distinguish different communication data messages.
 Protocol identifier: 00 00 means Modbus TCP protocol.
 Length: Indicates the next data length, in bytes.
For example:get DI state
01 00
Transaction ID
Protocol ID

4.10 Modbus RTU protocol data frame description

RTU frame format:
Device Address
1 Bit
For example:get DI state
01
Device Modbus address

4.11 MODBUS parameter configuration

4.11.1 DO register list

Register
Register function
address
DO state
0x0000
DO power-on
0x0064
state
DO operating
0x0578
mode
DO pulse width
0x05DC
DO follow the
0x0640
source
Copyright ©2012–2022,Chengdu Ebyte Electronic Technology Co.,Ltd
00 00
00 06
Length
Function Code
1 Bit
02
Function Code
Register
Quantity
type
Coil
Holding
register
Holding
register
Holding
register
Holding
register
01
Device Address
Data Segment
N Bit
00 00 00 04
Data Segment
Operation
Data Range/Remarks
Write to change the
current DO state, read
4
RW
to get the current DO
state
The default state of the
4
RW
coil after power-on
0x0000 level no follow
mode
4
RW
0x0001 pulse no follow
mode
0x0002 follow mode
4
RW
Range:50~65535ms
Range:
4
RW
0x0000: follow DI1
0x0001: follow DI2
ME31-AAAX2240_UserManul_EN
02
00 00 00 04
Function Code
Data Segment
Check code CRC
2 Bit
79 C9
CRC check code
Related
function codes
R:0x01
W: 0x0F、 0x05
R:0x01
W: 0x0F、 0x05
R:0x03
W: 0x06、 0x10
R:0x03
W: 0x06、 0x10
R:0x03
W: 0x06、 0x10
22

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents