Heating & Cooling Operating Envelope - York AFFINITY OptiHeat YAW040 Installation Manual

Geothermal heat pumps single speed hydronic with vapor injection
Table of Contents

Advertisement

AFFINITY SINGLE STAGE HYDRONIC WITH OPTIHEAT INSTALLATION MANUAL
Heating Operating Envelope
165
Operation Not Allowed
155
Caution: Sensitive Operating Range
145
135
125
115
105
95
85
75
65
20
30
If you are experiencing E10 faults caused by the thermal limit in the compressor being tripped and the unit is operating in or
close to the "Sensitive Operating Range" you may need to increase load water flow or decrease the set point. Increasing the
load water flow will lower the discharge pressure and compressor temperature.
Cooling Operating Envelope
Safe Operating Range
40
50
60
Source Entering Temperature,
New
70
80
90
o
F
38
100