Komfovent RHP STANDARD Series Installation Manual
Komfovent RHP STANDARD Series Installation Manual

Komfovent RHP STANDARD Series Installation Manual

Hide thumbs Also See for RHP STANDARD Series:

Advertisement

Quick Links

RHP STANDARD
INSTALLATION MANUAL
EN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RHP STANDARD Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Komfovent RHP STANDARD Series

  • Page 1 RHP STANDARD INSTALLATION MANUAL...
  • Page 3: Table Of Contents

    8. COMMISSIONING AND INSPECTION OF THE UNIT .................................... 30 8.1. Control panel C5.1 ................................................ 30 8.2. Starting the Unit With a Computer ........................................32 8.3. Quick Inspection ................................................34 UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 4: Introduction

    If heating/cooling capacity is still too low, additional heaters or coolers may be activated. Heat pump Rotary refrigerant heat Filter coil exchanger Filter Heat pump Heat pump Electrical assembly refrigerant coil heater Depends on configuration. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 5: Integrated Heat Pump

    (condenser and evaporator) and separate con- trol electronics: RHP 400 - RHP 600 RHP 800 3(4) 3(5) UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 6 17. Refrigerant coil positioned in the extract airflow 9. Defrost valve (SVD) 18. Refrigerant coil positioned in the supply airflow Fig. 1. Heat pumps hydraulic diagram UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 7 19. Buffer tank 9. Defrost valve 20. Liquid receiver 10. High pressure pressostat 21. Crankcase heating element 11. Low pressure pressostat Fig. 2. Heat pump assembly UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 8 Heat pump is not operating when outdoor air temperature is between 15°C and 20°C, as, in this case, the rotary heat exchanger is usually capable of reaching desired air temperature. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 9: Unit Types By Duct Connections

    Horizontal unit Vertical unit Fig. 4. Classification of units by duct connection Fig. 5. Relocation of duct connections of the universal units Depends on configuration. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 10: Unit Types By Inspection Sides

    11 – Main board of the C5 control panel – extract air 6 – Exhaust air refrigerant coil 12 – Main power cable location – exhaust air Depends on your order. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 11 11 – Main board of the C5 control panel – extract air 6 – Exhaust air refrigerant coil 12 – Main power cable location – exhaust air UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 12 11 – Main board of the C5 control panel – extract air 6 – Exhaust air refrigerant coil 12 – Main power cable location – exhaust air UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 13 11 – Main board of the C5 control panel – extract air 6 – Exhaust air refrigerant coil 12 – Main power cable location – exhaust air UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 14 11 – Main board of the C5 control panel – extract air 6 – Exhaust air refrigerant coil 12 – Main power cable location – exhaust air UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 15: Unit Transportation And Storage

    (dust, rain, cold, etc.). UAB KOMFOVENT is not responsible for losses caused by the carrier during transportation and unloading. UAB KOMFOVENT we reserve the right to make changes without prior notice...
  • Page 16: Mechanical Installation

    (e.g., in case of complex repairs). ≥300 ≥ ≥B Fig. 8. Device inspection area Except RHP 400 and RHP 600. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 17: Duct System Installation

    3 m Air exhaust vent min. 1 m Air intake vent min. 3 m min. 1,8 m min. 1,8 m UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 18 Duct diameter, mm Unit 400 V 450 V 600 U 700 V 800 U 1200 U 300×300 300×300 300×300 300×300 1600 U 300×300 300×300 300×300 300×300 UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 19: Connection Of External Heating/Cooling Units

    Therefore, it is necessary to connect a proper height siphon or a siphon with a one-way valve to the drain pipe. p < 0 H mm H/2 mm Fig. 10. Installation of a siphon Ordered separately. It is recommended to use PPU made by Komfovent. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 20: Outdoor Units

    5 – air shut-off dampers, 6 – additional air dampers for protection of a stopped unit The devices can only be installed outdoors by connecting their ducts horizontally. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 21: Technical Information

    800 UH Left L1 1648/1505 986/905 Right R1 1605/1505 995/905 1200 UH Left L1 1605/1505 995/905 Right R1 1605/1505 995/905 1600 UH Left L1 1605/1505 995/905 UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 22: Vertical Units

    All external electrical elements must be connected strictly according to the wiring diagram of the unit. • Do not disconnect the connectors by pulling wires or cables. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 23: Connection Of Electrical Components

    230V AC, 1A Common Water pump for heating 230V AC, 1A Fig. 15. Connection terminals for external components on the C5 main board UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 24 For the most accurate temperature measurement, sensor in a duct must be installed after all heating/cooling devices at least two duct diameters away from the nearest coil. >2D Fig. 18. Installation of a supply air temperature sensor UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 25: Control Panel Installation

    Do not use any other type or size screws but those that are supplied for control panel mounting. Wrong screws may cause damage to a circuit board. If the DX device was not predefined in the controller software, these outputs will be inactive. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 26 To the controller main board connect only the completely assembled control panel with back and front covers in- stalled. If installing covers when the control panel is powered up you may damage the internal electronic components. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 27: Connecting The Unit To The Local Computer Network Or The Internet

    Internet. In case of a computer, the unit is controlled via a web browser, and in case of a smart phone - via the Komfovent app. Use CAT5 type cable to connect your AHU to the computer network (RJ45 connection; see Fig. 14). The total cable length between the unit and the network router must not exceed 100 metres.
  • Page 28 502. Once a computer or smart phone is connected to the Internet, enter an external router IP address and set port number to your web browser or the Komfovent app to access the AHU user interface (for more information on control with a computer or smart phone see “User Manual”).
  • Page 29: Filters

    50% (M5) 805×400×46 1600 U Compact ePM1 60% (F7) 805×400×46 ePM10 50% (M5) 805×400×46 Depends on the order. Pageidaujant gali būti ePM1 60% (F7) klasė. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 30: Commissioning And Inspection Of The Unit

    If the unit is connected to the mains, the control panel will display a home screen or a screen saver that you can switch off with a single tap. Sold separately. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 31 To change the ventilation mode settings: select a desired mode and set a desired air volume or temperature with the arrows. Only for AHU with electronic TRV controller board. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 32: Starting The Unit With A Computer

    26 °C 100% AHU control Į On/Off Operation mode Economy1 Active functions Alarm status No alarms If the password was changed, use the changed password. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 33 3. Enter desired air flow and temperature in the selected mode settings. 4. Press “Save” button at the bottom of the screen. You can stop the unit by pressing ON/OFF button in the “Overview” window. UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 34: Quick Inspection

    The heat pump compressor operates properly, without any extraneous noise and vibrations. HP heat exchanger calibration performed (only in HP units) Other comments: Installer Company Tel. No. Date Signature UAB KOMFOVENT we reserve the right to make changes without prior notice RHP STANDARD_installation manual_24-10...
  • Page 36 SERVICE AND SUPPORT PARTNERS LITHUANIA J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at UAB KOMFOVENT Phone: +370 5 200 8000 Ventilair group www.ventilairgroup.com service@komfovent.com ACB Airconditioning www.acbairco.be www.komfovent.com REKUVENT s.r.o. www.rekuvent.cz FINLAND Komfovent Oy WESCO AG www.wesco.ch Muuntotie 1 C1 FI-01 510 Vantaa, Finland SUDCLIMATAIR SA www.sudclimatair.ch...