Function
This isolated barrier is used for intrinsic safety applications. It transfers digital signals (NAMUR sensors/mechanical contacts) from a hazardous
area to a safe area.
The proximity sensor or switch controls a passive transistor for the safe area load. The module output changes state when the input signal
changes state. The normal output state can be reversed with the selector switches on the side of the unit.
Line fault detection (LFD) can be selected or disabled via a selector switch.
During an error condition, the transistor reverts to its de-energized state and the LEDs indicate the fault. A separate fault output bus is available.
The fault conditions can be monitored via a Fault Indication Board.
This module mounts on a HiD Termination Board.
Connection
1.5 kΩ
I
10 kΩ
1.5 kΩ
II
10 kΩ
1.5 kΩ
III
10 kΩ
1.5 kΩ
IV
10 kΩ
Zone 0, 1, 2
Div. 1, 2
Technical Data
General specifications
Signal type
Functional safety related parameters
Safety Integrity Level (SIL)
Supply
Connection
Rated voltage
Rated current
Power dissipation
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
Switch Amplifier
HiD2844
<
4-channel isolated barrier
<
24 V DC supply (bus powered)
<
Dry contact or NAMUR inputs
<
4 passive transistor outputs
<
Line fault detection (LFD)
<
Up to SIL 2 acc. to IEC/EN 61508
HiD2844
SL2
+
1
5a
-
4
5b
+
2
1a
-
5
1b
+
3
3a
-
6
3b
+
7
7a
-
8
7b
1a, 1b
2a, 2b
Termination Board
Digital Input
SIL 2
SL1: 1a(-), 1b(-); 2a(+), 2b(+)
U
20.4 ... 30 V DC bus powered via Termination Board
r
I
15 mA at 24 V (per channel)
r
0.35 W at 24 V (per channel)
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
SL1
8a
11
+
I
7a
14
-
10a
12
+
II
9a
15
-
9b
13
+
III
10b
16
-
8b
17
+
IV
7b
18
-
-
24 V DC
+
FAULT
6b
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com
1