Function
This isolated barrier is used for intrinsic safety applications.
The device transfers digital signals (NAMUR sensors/mechanical contacts) from the explosion-hazardous area to the non-explosion-
hazardous area.
Each input controls a passive transistor for the non-explosion-hazardous area load.
Via switches the mode of operation can be reversed and the line fault detection can be switched off.
During a fault state, the transistors revert to their de-energized state and LEDs indicate the fault according to NAMUR NE 44. A separate fault bus
is available. This fault bus can be monitored if the termination board supports a module fault detection.
This device mounts on a HiC termination board.
Connection
1.5 kΩ
I
10 kΩ
1.5 kΩ
II
10 kΩ
Zone 0, 1, 2
Technical Data
General specifications
Signal type
Functional safety related parameters
Safety Integrity Level (SIL)
Systematic capability (SC)
Connection
Rated voltage
Ripple
Rated current
Refer to "General Notes Relating to Pepperl+Fuchs Product Information".
Pepperl+Fuchs Group
USA: +1 330 486 0002
www.pepperl-fuchs.com
pa-info@us.pepperl-fuchs.com
Switch Amplifier
HiC2842
<
2-channel isolated barrier
<
24 V DC supply (bus powered)
<
Dry contact or NAMUR inputs
<
2 passive transistor outputs
<
Line fault detection (LFD)
<
Reversible mode of operation
<
Up to SIL 2 (SC 3) acc. to IEC/EN 61508
HiC2842
SL2
+
1
5a
-
4
5b
+
2
1a
-
5
1b
1a, 1b
2a, 2b
Termination Board
Digital Input
SIL 2
SC 3
SL1: 1a(-), 1b(-); 2a(+), 2b(+)
U
19 ... 30 V DC bus powered via Termination Board
r
≤ 10 %
I
≤ 30 mA
r
Germany: +49 621 776 2222
pa-info@de.pepperl-fuchs.com
SL1
+
8a
11
I
7a
14
-
+
10a
12
II
-
9a
15
-
24 V DC
+
Fault
6b
Singapore: +65 6779 9091
pa-info@sg.pepperl-fuchs.com