Temperature Correction - Fujitsu ASUH15LPAS Installation Manual

Wall-mounted type
Table of Contents

Advertisement

■ External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function
Setting
number
value
00
Operation/Stop mode 1 (R.C. enabled)
01
46
02
03
Operation/Stop mode 2 (R.C. disabled)
■ Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01). This function will only work if the function setting 42 is set at "Both" (01)
Function
Setting
number
value
00
48
01
■ Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when
the outdoor unit is stopped during cooling operation.
Function
Setting
number
value
00
49
01
02
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02: Enable or disable this function by remote controller setting.
*When using a wired remote controller without Indoor unit fan control for energy saving for
cooling function, or when connecting a single split converter, the setting cannot be made
by using the remote controller. Set to (00) or (01).
To confi rm if the remote controller has this function, refer to the operation manual of each
remote controller.
■ Switching functions for external output terminal
Functions of the external output terminal can be switched.
Function
Setting
number
value
00
01 to 08
(Refer to the Design & technical manual.)
60
09
10
11
■ Control switching of external heaters
Sets the control method for the external heater being used. For details of the control method,
refer to the Design & Technical Manual.
Function
Setting
number
value
00
01
02
03
Heater selection control using outdoor temperature 1
04
Heater selection control using outdoor temperature 2
61
05
Auxiliary heater control by outdoor temperature 3
06
07
Auxiliary heat pump control by outdoor temperature 1
08
Auxiliary heat pump control by outdoor temperature 2
09
Auxiliary heat pump control by outdoor temperature 3
■ Standby time for auxiliary equipment operation
Sets the standby time until the auxiliary equipment operation starts during primary equip-
ment operation.
Function
Setting
number
value
00
01
71
02 to 98
99
(♦... Factory setting)
Setting description
(Setting prohibited)
Forced stop mode
(♦... Factory setting)
Setting description
Both
Wired remote controller
(♦... Factory setting)
Setting description
Disable
Enable
Remote controller
(♦... Factory setting)
Setting description
Operation status
Other status
Error status
Interlocked with indoor fans
External heater output
(♦... Factory setting)
Setting description
Auxiliary heater control 1
Auxiliary heater control 2
Heat pump prohibition control
Auxiliary heat pump control
(♦... Factory setting)
Setting description
Disable
1 minutes
2 minutes to 98 minutes
99 minutes
■ Heat pump backup setting
Enables or disables the heat pump backup instruction from the outdoor unit.
This function will be usable provided that the corresponding outdoor unit is connected.
Function
Setting
number
value
72
■ Emergency heat for external output terminal
Enables or disables emergency heat input.
To use this function, select "External heater output" after entering "Function Number 60". For
more information, Refer to the Design & technical manual.
Function
Setting
number
value
73
■ Setting record
Record any changes to the settings in the following table.
Function
number
11
Filter sign
40
Auto restart
42
Room temperature sensor switching
44
Remote controller custom code
46
External input control
48
Room temperature sensor switching (Aux.)
49
Indoor unit fan control for energy saving for cooling
60
Switching functions for external output terminal
61
Control switching of external heaters
71
Standby time for auxiliary equipment operation
72
Heat pump backup setting
73
Emergency heat for external output terminal
After completing the Function Setting, be sure to disconnect the power supply and then recon-
nect it.

5.2. Temperature correction

NOTES:
When changing Function 95, perform this setting before other Room temp. control settings
(Function 30, 31, 35, 36).
If Function 95 is not set fi rst, Room temperature control settings (Function 30, 31, 35, 36)
will be reset and you must re-do them again.
■ Heat Insulation condition (building insulation)
Heat insulation conditions diff er according to the installed environment.
"Standard insulation" (00) allows system to rapidly respond to the cooling or heating load
changes.
"High insulation" (01) is when the heat insulation structure of the building is high and does
not require system to rapidly respond to cooling or heating load changes.
When "High insulation" (01) is selected;
• Overheating (overcooling) is prevented at the start-up.
• All room temp. control settings (Function 30, 31, 35, 36) will reset to "No correction" [0.0°F
(0.0°C)].
Function Number
95
■ Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may
be required.
Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of room temp. sensor - correction temp. value
Example of correction :
When the temperature of room temp. sensor is 78 °F and the setting value is
"03" (-2 °F), the corrected temp. will be 80 °F (78 °F [-2 °F]).
The temperature correction values show the diff erence from the "Standard setting" (00)
(manufacturer's recommended value).
(♦... Factory setting)
Setting description
00
Disable
01
Enable
(♦... Factory setting)
Setting description
00
Disable
01
Enable
Setting description
(♦... Factory setting)
Setting
Setting Description
Value
00
Standard insulation
01
High insulation
(♦... Factory setting)
Setting value
En-11