Toshiba RAV-GM901CTP Series Service Manual page 63

Table of Contents

Advertisement

DN
Item
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
Louver type
19
(Adjustment of air direction)
In automatic cooling/heating, temp.
width of cool → heat, heat →
1E
cool mode selection control point
28
Automatic reset of power failure
Selection of option / error input
2A
(TCB-PCUC1E)
Selection of thermostat output
2b
(TCB-PCUC1E)
2E
Selection of HA (T10) terminal
31
Vent fan (Single operation)
32
Sensor selection
High ceiling selection
5d
(Air volume selection)
60
Timer setting (Wired remote controller)
Function selection CODE No. (DN) list
Contents
0
0
0
: 0
N
o
n
e
0002: 2500H
0004: 10000H
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
to
0099: Undecided
0000: No shift
0002: +2°C
to
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0007: Ceiling
0000: Undecided
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit in group
0000: No louver model
0002: 1-way
0004: 4-way
0000: 0 deg
to
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0
0
0
: 0
N
o
n
e
0000: Filter input
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0002: Fire alarm input
0000: Impossible
0000: Body TA sensor
Model RAV-
Standard
Up to 3.5 m
(Factory default)
High ceiling (1)
Up to 4.3 m
0000: Operable
- 63 -
0
0
0
: 1
1
5
0
H
0003: 5000H
0005: Clogging sensor used
0064: No.64 unit
0001: +1°C
0010: +10°C
(Up to +6 is recommended.)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Master unit in group
0001: Swing only
0003: 2-way
0010: 10 deg
0
0
0
: 1
r P
v o
d i
e
d
0001: Alarm input
(Air cleaner, etc.)
0001: Card input
(Forgotten to be off)
0001: Possible
0001: Remote controller sensor
SET
GM901
DATA
0000
0003
0001: Operation prohibited
At shipment from factory
According to type
0000: Standard
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
According to model type
0003: 3 deg
(Ts±1.5)
0000: None
0002: Humidifier
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Body sensor
0000: Standard
0000: Operable