Outing Function

Outing function is a function that prevents the room temperature from
increasing too much (or decreasing too much) when no one is in the room.
An air conditioner works automatically if this function is set effective.
General Performance of the Outing Function
COOL / DRY
The air conditioner starts operation when the
1
room temperature increases up to –1°C of the
upper limit.
The air conditioner stops operation when the
2
room temperature decreases up to –2°C of the
upper limit.
HEAT
The air conditioner starts operation when the
1
room temperature decreases up to +1°C of the
lower limit.
The air conditioner stops operation when the
2
room temperature increases up to +2°C of the
lower limit.
[Precautions]
• The outing control only starts/stops the air conditioner. It does not change the
operation mode/temperature setting.
Therefore, the operation mode/temperature needs to be set beforehand so that
the outing function turns on the air conditioner with your desired operation mode/
temperature setting.
• If the room temperature rapidly changes, the room temperature may get over the
upper or lower limit when the outing function is activated.
• The outing function is invalid during FAN/AUTO operation mode.
• The air conditioner's stop order (stated in
function is operated.
If operated using other remote control unit (or a centralized control device such as a
system control), the outing function does not work.
• Outing function indication
Outing function
indication
Off
Flashing
Lighting
Note
A remote controller may lose outing function operation information when it is cut for
more than 24 hours during the outing function operation by electricity. It reverts from
the blackout, and an air conditioner does not drive in outing function when operation
is started. At this time, an air conditioner does not stop at outing function.
16
The outing function is not set.
The outing function is now being set or under operation.
Although the outing function is set, it is not under operation.
Outing function upper limit
1
Room temperature
Room temperature
1
Outing function Lower limit
/ above) is valid only when the outing
2
Status
1°C
1°C
2
2
1°C
1°C

Advertisement

Table of Contents
loading