  • Page 1 Manual Inverter (with firmware xxxx400 or higher) 12 | 3000 | 120V 24 | 3000 | 120V...
  • Page 3: Safety Instructions

    1. SAFETY INSTRUCTIONS In general Please read the documentation supplied with this product first, so that you are familiar with the safety signs en directions before using the product. This product is designed and tested in accordance with international standards. The equipment should be used for the designated application only.
  • Page 4: Transport And Storage

    Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts, curtains or other textiles, etc. in the immediate vicinity of the equipment. Transport and storage On storage or transport of the product, ensure that the battery leads are disconnected. No liability can be accepted for damage in transit if the equipment is not transported in its original packaging.
  • Page 5 2. DESCRIPTION SinusMax - Superior engineering Developed for professional duty, this range of inverters is suitable for the widest range of applications. The design criteria have been to produce a true sine wave inverter with optimised efficiency but without compromise in performance. Employing hybrid HF technology, the result is a top quality product with compact dimensions, light in weight and capable of supplying power, problem-free, to any load.
  • Page 6: Operation

    3. OPERATION 3.1 On/Off Switch When switched to "on", the product is fully functional. The inverter will come into operation and the LED "inverter on" will light up. 3.2 Remote control Remote control is possible with a simple on/off switch or with an Inverter Control panel.
  • Page 7 Inverter inverter on overload The inverter is switched off due to overload or short circuit. low battery temperature Inverter inverter on overload The battery is almost fully exhausted. low battery temperature Inverter inverter on overload The inverter has switched off due to low battery voltage.
  • Page 8 Inverter inverter on The inverter has switched off due to overload the electronics temperature being too high. low battery temperature Inverter inverter on -If the LEDs are flashing alternately, the battery is nearly exhausted and overload the nominal output is exceeded. -If "overload"...
  • Page 9: Installation

    4. INSTALLATION This product may only be installed by a qualified electrical engineer. 4.1 Location The product must be installed in a dry and well-ventilated area, as close as possible to the batteries. There should be a clear space of at least 10cm around the appliance for cooling.
  • Page 10: Connection Of Battery Cables

    4.2 Connection of battery cables In order to utilize the full capacity of the product, batteries with sufficient capacity and battery cables with sufficient cross section should be used. See table. 12/3000 24/3000 Recommended battery capacity (Ah) 400–1200 200–700 Recommended DC fuse 400A 300A Recommended cross-section (mm...
  • Page 11 4.3 Connection of the AC cabling This is a Safety Class I product (supplied with a protective grounding terminal). The neutral output of the inverter is connected to the enclusure. This to ensure proper functioning of a GFCI (or RCCB) to be installed in the AC output of the Inverter.
  • Page 12 4.4.3 Parallel Connection The Inverter can be connected in parallel with several identical devices. To this end, a connection is established between the devices by means of standard RJ45 UTP cables. The system (Two or more Inverters plus optional control panel) will require subsequent configuration (see Section 5).
  • Page 13 5. CONFIGURATION Settings may only be changed by a qualified electrical engineer. • • Read the instructions thoroughly before implementing changes. 5.1 Standard settings: ready for use On delivery, the Inverter is set to standard factory values. In general, these settings are suitable fo stand-alone operation.
  • Page 14: Configuration By Computer

    Search Mode (Applicable in stand-alone configuration only) If search mode is ‘on’, the power consumption in no-load operation is decreased by approx. 70%. In this mode the inverter is switched off in case of no load or very low load, and switches on every two seconds for a short period. If the output current exceeds a set level, the inverter will continue to operate.
  • Page 15 5.3.1 VE.Bus Quick Configure Setup VE.Bus Quick Configure Setup is a software program with which systems with a maximum of three Inverters (parallel or three phase operation) can be configured in a simple manner. VEConfigure3 forms part of this program. You can download the software free of charge at www.victronenergy.com .
  • Page 16 Remarks: - DIP switches ds8,ds7 ,ds6 ,ds2 and ds1 are not assigned and should remain off. - The DIP switch functions are described in 'top to bottom' order. Since the uppermost DIP switch has the highest number (8), descriptions start with the switch numbered 5. - These settings are not relevant for slaves.
  • Page 17 5.4.5 Examples Example 1 shows the factory setting (since factory settings are entered by computer, all DIP switches of a new product are set to ‘off’). examples of settings: DS-8 not used DS-8 DS-8 DS-8 DS-7 not used DS-7 DS-7 DS-7 DS-6 not used DS-6...
  • Page 18: Maintenance

    Avoid moisture and oil/soot/vapours, and keep the device clean. 7. FAULT INDICATIONS With the procedures below, most errors can be quickly identified. If an error cannot be resolved, please refer to your Victron Energy supplier. 7.1 General error indications Problem Cause...
  • Page 19 7.2 VE.Bus LED indications Inverters included in a VE.Bus system (a parallel or 3-phase arrangement) can provide so-called VE.Bus LED indications. These LED indications can be subdivided into two groups: OK codes and error codes. 7.2.1 VE.Bus OK codes If the internal status of a device is in order but the device cannot yet be started because one or more other devices in the system indicate an error status, the devices that are in order will indicate an OK code.
  • Page 20: Technical Specifications

    8. TECHNICAL SPECIFICATIONS Inverter 12/3000 24/3000 INVERTER Input voltage range (V DC) 9,5 – 17 19 – 33 Output Output voltage: 120 VAC ± 2% Frequency 60 Hz ± 0,1% Cont. output power at 25°C (VA) 3000 Cont. output power at 25°C (W) 2400 Cont.
  • Page 21 APPENDIX A Overview connections INVERTER 3k B 2x RJ45 connector for remote control and/or parallel / three-phase operation. C Load connection. 3K model AC out: (left to right): L (phase), N (neutral), PE (ground). E Battery minus. Double M8 battery minus connection. Battery plus.
  • Page 22: Appendix B: Block Diagram

    APPENDIX B: Block diagram See table in Chapter 4.2 “Recommended DC fuse”.
  • Page 23: Appendix C: Parallel Connection

    APPENDIX C: Parallel connection APPENDIX D: Three phase connection...
  • Page 24: Appendix G: Dimensions

    APPENDIX G: Dimensions...
  • Page 25 Dimensions 3k cabinet...
  • Page 26 Victron Energy Blue Power Distributor: Serial number: Version : 01 Date : September 20 , 2023 Victron Energy B.V. De Paal 35 | 1351 JG Almere PO Box 50016 | 1305 AA Almere | The Netherlands E-mail : sales@victronenergy.com www.victronenergy.com...