Commissioning an external fan

The external fan ensures that the machine is cooled irrespective of the machine speed or
direction of rotation. The external fan is only suitable for one direction of rotation.
Checks before the first test run
Before the first test run, carry out the following checks:
● The external fan is correctly fitted and aligned.
● The rotor runs freely.
● All of the retaining elements and electrical connections are securely tightened.
● The grounding and equipotential bonding connections to the mains have been correctly
● The air flow is not impeded or shut off by flaps, covers or similar.
● If the cooling air is in open circulation, it has only weak, chemically abrasive properties and
● All protection measures have been taken to prevent accidental contact with moving or live
Performing the test run
1. Switch the external fan motor on and off briefly.
2. Compare the direction of rotation of the external fan with the specified direction of rotation.
3. If the direction of rotation is wrong, then interchange two line cables in the external fan motor
SIMOTICS FD 1LQ1
Operating Instructions 01/2019
made.
a low dust content.
parts.
The direction of rotation of the external fan is indicated with an arrow on the fan cover
specifying the direction of rotation or with a terminal designation on the rating plate of the
external fan unit.
Depending on the version, the fan impeller is visible through the air inlet opening in the fan
cover on the external fan motor.
terminal box.
7.6 Commissioning an external fan
Start-up
95