Duct Mounting; Mounting With Flange; Minimum Immersion Depth; Mounting With Immersion Well - E+E Elektronik EE431 User Manual

Duct and immersion temperature sensor
Table of Contents

Advertisement

4.1

Duct Mounting

4.1.1.

Mounting with flange

Mount the sensor about one meter from the inlet
Mount the probe in a way, that the probe tip is placed in the middle of the duct
Ø > 16
Ø > 0.63
Fig. 3
Correct position of the probe in a flange
4.1.2.

Minimum Immersion Depth

Placement options
Fig. 4
Correct position in a pipe
4.1.3.

Mounting with Immersion Well

Fig. 5
Handling of the immersion well
Procedure:
1.
The spring inside the well must be removed and replaced by a standard M12x1.5 cable gland
(not included in the scope of supply).
2.
Insert the sensor and fix it by fastening the cable gland.
NOTICE
Observe the operating temperature range of the cable gland to match the process parameters.
6
0.24
Temperature sensor
Temperature sensor
Min. 50 mm (1,97")
Min. 50 mm (1,97")
1.
User Manual EE431
Temperature sensor
Temperature sensor
Flow
Flow
2.
Duct and Immersion Temperature Sensor | 10