TIMER FEATURES

Remote Lock
The timer does not allow the unit/system to go into
Regeneration until the Regeneration Lockout Input signal to the
unit is cleared. This requires a contact closure to activate the
unit. The recommended gauge wire is 16 AWG with a maximum
wire length run of 50 feet.
Regeneration Day Override Feature
If the Day Override option is turned on and the valve reaches
the set Regeneration Day Override value, the Regeneration
Cycle starts if no other unit is in Regeneration. If other units
are in regeneration, it is added to a regeneration queue. This
occurs regardless of the remaining volume available.
Lock Settings (access to Master Programming)
Lock Settings prevents the user from accessing Master
Programming. In Master Programming, select the desired Lock
Settings option (Off, Time Based, Delayed, or Enter Code).
Time Based - User must set clock to 12:01 pm to unlock
Delayed - User must press and hold the Left and Down buttons
for 60 continuous seconds to unlock
Enter Code - User must input code "1201" to unlock
Capacitive Buttons
Capacitive button entry warrant different consideration than
tactile button entry. Do not wear gloves. Be sure to keep
your hands and the capacitive buttons free of debris, grease,
or water. Buttons may become temporarily unresponsive if
environmental conditions change such as sudden humidity or
temperature changes. If buttons become unresponsive, wait 5
to 10 minutes for the buttons to recalibrate.
LED Status indicator
Blue - Unit in Service
Flashing Blue - Regeneration Queued
Green - Unit in Regeneration
Flashing Green - Unit in Standby
Red - Error with codes
Power Loss Backup
Time of day super capacitor backup for power loss; rated to
last minimum 12 hours
Continuous Flow Detect
Alert appears when specified continuous flow rate is detected
during service over a specified duration. Continuous flow rate
is adjustable from 0.1 to 99999.9 GPM/LPM (accuracy of flow
rate detected will vary based on capability of meter). Duration
range is adjustable from 1 to 255 hours.
Remote Regeneration
Ability to trigger a regeneration via a remote input.
6 • Pentair Fleck NXT2 Timer
Regeneration Types
Softener/Filter Meter Delayed - When volume remaining
reaches zero and the scheduled regeneration time is reached
(default 2 a.m. softener; 12 a.m. filter), the unit will regenerate.
Softener/Filter Meter Immediate - When volume remaining
reaches zero, the unit will regenerate.
Time Clock - Once days remaining reaches zero the unit will
regenerate at the selected regeneration time (default 2 a.m.
softener; 12 a.m. filter).
Day of the Week - Once selected day of the week is reached it
will regenerate at the selected regeneration time.
Remote Regeneration - Remote Regeneration is accomplished
by a 3rd party device completing a contact closure connected to
the remote regeneration input connector. The 3rd party device
must complete the signal duration time that was set in the
duration signal time in programming to start a regeneration.
You can set the remote regeneration for immediate
regeneration or delayed regeneration at the set time that was
programmed for regeneration time in programming.
Reset to Factory Defaults
While powering up the unit, when the Pentair logo appears,
press and hold the Extra Cycle button to access the Reset
menu then select Reset to Factory Defaults. Press the Extra
Cycle Button to confirm your selection and to advance to the
service screen. Furthermore, you may select
Reset to Non-Factory Defaults to save a set of unique control
parameters.
Power on the unit.
When Pentair logo appears,
press and hold the Extra Cycle button.
The Reset menu appears.
PRESS & HOLD
Use the up/down buttons to select.
RESET
BACK
RESET TO FACTORY DEFAULTS
RESET TO NON-FACTORY DEFAULTS
Press the Extra Cycle button to set the
desired option and return to the
Service screen.
END
Lock Window
Lock Window prevents the unit from regenerating during a
specified time frame. Two lock windows are available (Lock
Window #1 and Lock Window #2). In Master Programming,
enable a Lock Window then select the desired Lock Start time
and Lock End time.
Settings Review
To prevent unintentional changes to Master Programming,
enable Settings Review to view and navigate through Master
Programming settings without the ability to edit.
TIMER FEATURES continued...
Push Settings
The ability to transmit user settings from one unit to all other
connected units. Select the desired Master Programming
settings on one unit then push the same settings to all other
connected units. After the push settings have completed, you
may still make unique changes to individual units.
Auxiliary Relays
The NXT2 has two auxiliary relays that may be activated based
on cycle, time, or volume.
Activates during selected cycle step
AUX.1: CYCLE BASED
SP
BW
BD
RR
RF
SB
Activates upon selected start time
AUX.1:TIME BASED-START TIME #1
(Range: 0-91 minutes)
1 M
Deactivates upon selected end time
AUX.1:TIME BASED-END TIME #1
(Range: Start Time plus 1 minute)
5 M
Activates when selected volume (gallon)
AUX.1:VOLUME BASED - VOLUME-G
is reached (Range: 0-99999)
00100
Selected duration in seconds
AUX.1:VOLUME BASED - DURATION-S
(Range: 0-9999 seconds)
0010
Pentair Fleck NXT2 Timer • 7