INTRODUCTION
The DKN509 Wireless Communicating Thermostat is integral to the SiteLine™ for Wireless
BAS (building automation system). Combined with the Central Controller and wireless
communicating sensors, they provide building managers and occupants easy, wall-
mounted comfort control. Built into the Wireless Thermostat are sensors for monitoring
indoor air quality (IAQ), light, sound, and occupancy.
PACKAGE CONTENTS
DKN509 Wireless Communicating Thermostat
Mounting accessories
SPECIFICATIONS
Power
Operating range
Communication
Inputs
IM 1339-1 • DKN509 Wireless Thermostat
Power Source: 24V AC/DC input (+/- 15%)
Peak consumption (wireless communicating thermostat): 1.4VA
Maximum
Peak consumption, 1W nominal (1.3W maximum) power
consumption
Temperature 0 to 122°F (-17 to 50°C)
Humidity 20-85% non-condensing.
900-928 MHz Mesh IEEE 802.15.4-compliant, for communications
to CCU
Bluetooth: BLE 4.1 for commissioning, triangulation and
communication to wireless sensors
3-wire sensor bus for daisy-chained sensor communication and
low power 3V dc
4-wire interface for RS 485 communication @ 115200 baud and
5V DC, 100mA power source
2 x 10K Type-2 thermistor inputs with 2% accuracy
2 x 0-10V Analog voltage inputs with 2% detection accuracy (2-
10V)
Touch slider for temperature control along with 3 mechanical
buttons
www.DaikinApplied.com

Advertisement

loading

Summary of Contents for Daikin DKN509

  • Page 1 DKN509 Wireless Communicating Thermostat INTRODUCTION The DKN509 Wireless Communicating Thermostat is integral to the SiteLine™ for Wireless BAS (building automation system). Combined with the Central Controller and wireless communicating sensors, they provide building managers and occupants easy, wall- mounted comfort control. Built into the Wireless Thermostat are sensors for monitoring indoor air quality (IAQ), light, sound, and occupancy.
  • Page 2: Warnings And Disclaimers

    The following compiles a list of warnings and notes associated with the installation and operation of this kit. Make sure to follow these warnings, as well as always having properly trained technicians and electricians, or Daikin-authorized technicians perform work. ⚠...
  • Page 3 MOUNTING 1. Controller connection plate 5. Rubber cover 2 2. Wireless communicating thermostat 6. Gang box 3. Allen head screws 7. PHP screws 4. Rubber cover 1 8. Back plate IM 1339-1 • DKN509 Wireless Thermostat www.DaikinApplied.com...
  • Page 4 DAIKIN WIRELESS TECHNICAL SUPPORT Installations carried out by non-certified technicians/engineers would void warranty. For more information on wiring, commissioning, or usage of Daikin Wireless products, please refer to any documentation provided with the job. If no documentation was provided with the job, please use the Daikin Wireless Help Center (support.wirelesscontrols.daikinapplied.com) where you can find application specific...
  • Page 5: Canadian Compliance Statement

    REMARQUE: Cet équipement est conforme aux limites d'exposition aux radiations RSS- 102 établies pour un environnement non contrôlé. Cet équipement doit être installé et utilisé à une distance minimale de 20 cm entre le radiateur et votre corps. IM 1339-1 • DKN509 Wireless Thermostat www.DaikinApplied.com...
  • Page 6 ©2023 Daikin Applied, Minneapolis, MN. All rights reserved throughout the world. IM 1339-1 • DKN509 Wireless Thermostat www.DaikinApplied.com...