Connection Instructions -Refrigerant Piping; Cut Pipe; Remove Burrs - Pioneer FYB018GMFILCAD Owners And Installation Manual

Table of Contents

Advertisement

CAUTION
Oil traps
If oil flows back into the outdoor unit's
compressor, this might cause liquid
compression or deterioration of oil return.
Oil traps in the rising gas piping can prevent
this.
An oil trap should be installed every 6m(20ft)
of vertical suction line riser
(<36000Btu/h unit).
An oil trap should be installed every
10m(32.8ft) of vertical suction line riser
(≥36000Btu/h unit).
Indoor unit/
Outdoor unit
Page 30
Connection Instructions –
Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra
Indoor unit/
Outdoor unit
care to cut and flare them properly. This will
ensure efficient operation and minimize the
need for future maintenance.
1. Measure the distance between the indoor
2. Using a pipe cutter, cut the pipe a little longer
6m/20ft
(<36000Btu/h unit)
3. Make sure that the pipe is cut at a perfect 90°
10m/32.8ft
(≥36000Btu/h unit)
6m/20ft
(<36000Btu/h unit)
10m/32.8ft
(≥36000Btu/h unit)
Step 2: Remove burrs.
Burrs can a ect the air-tight seal of refrigerant
piping connection. They must be completely
removed.
1. Hold the pipe at a downward angle to
CAUTION
The branching pipe must be installed
horizontally. An angle of more than 10° may
cause malfunction.
DO NOT install the connecting pipe until
both indoor and outdoor units have been
installed.
Insulate both the gas and liquid piping to
prevent water leakage.
and outdoor units.
than the measured distance.
angle.
90°
Oblique Rough Warped
DO NOT DEFORM PIPE
WHILE CUTTING
Be extra careful not to damage, dent, or
deform the pipe while cutting. This will
drastically reduce the heating e ciency
of the unit.
prevent burrs from falling into the pipe.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fyb018gmfilcad-10

Table of Contents